York HVAC Catalogue 2018 EN 2019 EN | Page 111
YORK ® AIR-CONDITIONING PRODUCTS
YFCN-ECM Fan Coil Unit Inverter
with centrifugal fan
0.7 to 7.1 kW
Technical features
Model
Total cooling capacity [kW]
Sensible cooling capacity [kW]
Water flow in cooling [l/h]
(1)
(1)
(1)
Pressure drop in cooling [kPa]
Heating capacity 2 pipes [kW]
Water flow in heating 2 pipes [l/h] *
Pressure drop in heating 2 pipes [kPa]
Heating capacity 4 pipes [kW]
Water flow in heating 4 pipes [l/h]
Pressure drop in heating 4 pipes [kPa]
(1)
(2)
(2)
(2)
(3)
(3)
(3)
Air flow [m3/h]
Sound power level [dB(A)]
Sound pressure level [dB(A)]
(4)
230 240 430 440 630 640 730 740 930 940
max 10v 1.59 1.86 2.95 3.17 3.96 4.51 4.94 5.30 6.26 7.04
med 5v 1.18 1.32 2.18 2.27 2.93 3.19 3.68 3.82 4.82 5.21
min 1v 0.73 0.77 1.41 1.43 1.96 2.05 2.60 2.61 3.45 3.59
max 1.28 1.42 2.26 2.39 3.08 3.38 3.80 3.99 5.10 5.53
med 0.92 0.98 1.64 1.67 2.22 2.34 2.77 2.82 3.79 3.99
min 0.55 0.56 1.03 1.03 1.46 1.48 1.92 1.90 2.63 2.69
max 277 323 511 549 686 781 857 918 1 094 1 228
903
med 205 229 377 392 506 550 636 660 836 min 127 134 244 248 339 354 449 451 597 621
max 8.6 14.8 28.9 16.1 19 33 32.6 25.6 25.9 20.8
12.1
med 5.1 8 17 8.9 11.1 17.8 19.4 14.3 16.1 min 2.2 3.2 7.9 4 5.5 8.2 10.5 7.3 8.9 6.3
max 1.80 1.98 3.14 3.32 4.14 4.68 5.08 5.43 7.38 7.93
5.63
med 1.29 1.37 2.26 2.30 3.00 3.23 3.72 3.84 5.41 min 0.77 0.78 1.42 1.42 1.96 2.02 2.56 2.57 3.74 3.76
max 277 323 511 549 686 781 857 918 1 094 1 228
903
med 205 229 377 392 506 550 636 660 836 min 127 134 244 248 339 354 449 451 597 621
max 7.0 13.6 26.7 13.7 17.0 29.1 28.3 22.0 24.2 20.9
med 3.9 7.1 14.9 7.3 9.6 15.1 16.4 12.0 14.0 11.4
min 1.6 2.6 6.6 3.1 4.5 6.6 8.5 5.9 7.3 5.6
max 1.43 - 2.41 - 3.22 - 4.06 - 5.24 -
med 1.08 - 1.85 - 2.45 - 3.12 - 4.05 -
min 0.71 - 1.29 - 1.76 - 2.33 - 2.99 -
max 140 - 236 - 317 - 398 - 514 -
med 106 - 181 - 241 - 306 - 397 -
-
min 70 - 126 - 172 - 228 - 292 max 3.5 - 11.0 - 3.6 - 6.3 - 9.9 -
med 2.1 - 6.9 - 2.2 - 4.0 - 6.3 -
min 1.0 - 3.6 - 1.2 - 2.4 - 3.7 -
max 330 325 515 505 735 720 890 875 1 395 1 365
med 220 210 350 340 495 475 610 585 945 910
min 120 115 210 200 305 290 400 380 605 575
max 51 51 51 51 54 54 57 57 64 64
med 41 41 42 42 44 44 48 48 55 55
min 30 30 30 30 33 33 37 37 44 44
max 42 42 42 42 45 45 48 48 55 55
med 32 32 33 33 35 35 39 39 46 46
min 21 21 21 21 24 24 28 28 35 35
Power supply [V-ph-Hz]
230 / 1 / 50 + E
Power input [W] max 21 21 25 25 32 32 41 41 99 99
Absorbed current [A] max 0.18 0.18 0.22 0.22 0.28 0.28 0.34 0.34 0.81 0.81
Dimensions **
Height mm 530 530 530 530 530 530 530 530 530 530
Width mm 770 770 985 985 1 200 1 200 1 415 1 415 1 415 1 415
Depth mm 225 225 225 225 225 225 225 225 255 255
(1) Room temperature 27°C d.b., 19°C w.b. - Water temperature 7/12 °C
(2) Room temperature 20°C - Water temperature 45/40 °C
(3) Room temperature 20°C - Water temperature: 65/55°C
(4) The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m 3 room and a reverberation time of 0.5 sec.
* Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397 ** Dimensions refer to the units with casing
Manufacturer reserves the rights to change specifications without prior notice.
111