York HVAC Catalogue 2018 EN 2019 EN | Page 109
YORK ® AIR-CONDITIONING PRODUCTS
YFCN Fan Coil Unit centrifugal fan
0.7 to 7.4 kW
Technical features
Model
Total cooling capacity [kW]
Sensible cooling capacity [kW]
Water flow in cooling [l/h]
(1)
(1)
(1)
Pressure drop in cooling [kPa]
Heating capacity 2 pipes [kW]
Water flow in heating 2 pipes [l/h] *
Pressure drop in heating 2 pipes [kPa]
Heating capacity 4 pipes [kW]
Water flow in heating 4 pipes [l/h] *
Pressure drop in heating 4 pipes [kPa]
(1)
(2)
(2)
(2)
(3)
(3)
(3)
Air flow [m3/h]
Sound power level [dB(A)]
Sound pressure level [dB(A)]
(4)
140 240 340 440 540 640 740 840 max 1.20 1.78 2.53 3.08 4.03 4.71 5.48 6.34
940
7.42
med 1.00 1.41 1.87 2.25 3.21 3.81 4.56 5.63 6.41
min 0.65 1.00 1.63 1.81 2.17 2.79 3.51 3.97 4.79
max 0.94 1.35 1.86 2.30 3.01 3.52 4.13 4.93 5.87
med 0.77 1.05 1.36 1.65 2.36 2.81 3.39 4.33 4.98
min 0.49 0.73 1.18 1.32 1.58 2.03 2.57 2.98 3.63
max 212 311 442 537 703 824 960 1 113 1 307
med 175 246 325 392 559 664 798 986 1 125
min 115 174 284 315 377 487 612 693 839
max 5.6 13.9 11.5 15.5 31.3 36.2 27.7 32.2 23.2
med 4 9.1 6.7 9 20.8 24.8 20 26.0 17.8
min 1.9 4.9 5.3 6.1 10.4 14.4 12.5 14.0 10.6
8.52
max 1.31 1.83 2.59 3.14 4.01 4.92 5.59 7.20 med 1.07 1.43 1.87 2.27 3.16 3.90 4.62 6.27 7.18
min 0.69 0.99 1.62 1.80 2.10 2.82 3.49 4.26 5.23
max 212 311 442 537 703 824 960 1 113 1 307
med 175 246 325 392 559 664 798 986 1 125
min 115 174 284 315 377 487 612 693 839
max 5.3 11.8 9.8 12.8 25.2 31.8 23.2 31.7 23.7
med 3.7 7.6 5.4 7.2 16.6 21.1 16.6 24.9 17.6
min 1.7 4.0 4.2 5.0 8.1 11.9 10.1 12.8 10.0
max 0.91 1.33 1.99 2.33 3.00 3.33 4.20 4.75 5.46
med 0.77 1.09 1.56 1.81 2.50 2.79 3.59 4.26 4.79
min 0.55 0.83 1.40 1.52 1.84 2.19 2.89 3.16 3.71
max 78 114 171 200 258 287 361 408 470
med 66 94 134 156 215 240 309 366 412
min 47 71 120 131 158 188 249 272 319
max 1.3 3.1 7.8 10.3 3.2 3.8 6.7 8.3 10.7
8.5
med 1.0 2.2 5.1 6.6 2.3 2.8 5.1 6.9 min 0.5 1.3 4.2 4.9 1.3 1.8 3.5 4.1 5.4
max 220 295 385 485 650 760 925 1 200 1 500
med 175 220 270 335 495 590 735 1 020 1 210
min 105 145 235 265 315 415 535 655 830
max 45 47 49 47 48 52 56 60 64
med 39 40 40 39 41 46 51 56 58
min 32 30 36 33 31 37 42 45 50
max 36 38 40 38 39 43 47 51 55
med 30 31 31 30 32 37 42 47 49
min 23 21 27 24 22 28 33 36 41
Power supply [V-ph-Hz]
230 / 1 / 50 + E
Power input [W] max 33 40 49 57 61 88 103 130 176
Absorbed current [A] max 0.16 0.18 0.23 0.26 0.27 0.39 0.47 0.58 0.78
Dimensions **
Height mm 530 530 530 530 530 530 530 530 530
Width mm 670 770 985 985 1 200 1 200 1 415 1 415 1 415
Depth mm 225 225 225 225 225 225 225 255 255
(1) Room temperature 27°C d.b., 19°C w.b. - Water temperature 7/12 °C.
(2) Room temperature 20°C - Water temperature 45/40 °C. (3) Room temperature 20°C - Water temperature 65/55 °C.
(4) The sound pressure levels are 9 dB(A) lower than the sound power levels and apply to the reverberant field of a 100 m 3 room and a reverberation time of 0.5 sec.
* Water flow values as Cooling, accordingly to the EUROVENT standards and UNI ENV 1397.
** Dimensions refer to the units with casing.
Data shown is for 4 row cooling version, 2 pipe system.
For performance of 3 row cooling version please contact your local Johnson Controls sales office.
Manufacturer reserves the rights to change specifications without prior notice.
109