YORK ® AIR-CONDITIONING PRODUCTS
Single stage hot water driven absorption chiller
YHAU CL
Two Step Evaporator and Absorber Design
Efficiency, Reliability, Cost of Ownership
The innovative 2-step evaporator and absorber design is more efficient
than a conventional cycle. This ingenious design splits the absorption
process into two steps, similar to how a series-counter-flow
arrangement splits the work between two chillers. The result of the
design allows the YHAU-CL to perform the absorption function with
lower solution concentrations than conventional designs, increasing
efficiency and reliability, and decreasing cost of ownership.
Reliability is enhanced because the solution concentrations are lower
leaving the absorber, which allows the entire cycle to operate at lower
concentrations virtually eliminating the possibility of crystallization.
Efficiency is enhanced because the YHAU-CL can take advantage
of lower than normal hot water temperatures in the generator. This
is because at lower concentrations the solution will boil at a lower
temperature in the generator.
Lastly, total operating cost decreases because of the lower
concentration of the solution entering the generator, a wider
temperature range of hot water can be used, reducing pumping
horsepower.
Full Automatic Purging System
As a standard feature, the unit has a fully automatic purging system
comprising of electronic vacuum transmitter, solenoid valves and
trending capability that ensures design performance and improves
reliability. The operator does not have to worry about the sequence of
purging for removing the non-condensable gases.
Chiller control
The YHAU Control Center, standard on each chiller, provides the
ultimate in efficiency, monitoring, data recording, chiller protection and
operating ease.
The LCD display allows graphic animated display of the chiller, chiller
sub-systems and system parameters; this allows the presentation of
several operating parameters at once. In addition, the operator may view
a graphical representation of the historical operation of the chiller as well
as the present operation. The panel is capable of communication with
building management systems and is available in multiple languages.
Nominal capacity
YHAU CL Model
Cooling Capacity kW
COP (low temperature hot water)
YHAU CL Model
Cooling Capacity kW
COP (low temperature hot water)
30EXE 40EXE 50EXE 65EXE 80EXE 100EXE 130EXE 160EXE 200EXE 255EXE 320EXE 400EXE 500EXE
105
0,78 141
0,78 179 222 271 352 443 563 721 869 1125 1407 1758
0,78 0,78 0,78 0,76 0,78 0,78 0,78 0,78 0,78 0,78 0,78
630EXW 700EXW 800EXW 1934
0,78 2110
0,78 2461
0,78
900EXW 1000EXW 1120EXW 1250EXW 1400EXW 1500EXW 1600EXW 1680EXW 1800EXW 1900EXW 2000EXW
2708
0,78
3024
0,78
3411
0,78
3938
0,78 4431
0,78 4852
0,78 5134
0,78 5274
0,78 5626
0,78 5943
0,78
6153
0,78
At 6°C leaving chilled water, 90°C entering generator water, and 27°C entering condenser water.
Technical data
YHAU CL Model
Length
Dimensions Width
Height
Operating weight kg
mm
mm
mm
YHAU CL Model
Length
Dimensions Width
Height
Operating weight kg
mm
mm
mm
30EXE 40EXE 50EXE 65EXE 80EXE 100EXE 130EXE 160EXE 200EXE 255EXE 320EXE 400EXE 500EXE
1900 2200 2500 3100 2200 2600 3200
1800
2500
6100 3800 4600 3300 3900 4700 5700
10300 2200
3200
12200
14400 17400
1500
2100
2700 3100 3600
630EXW 700EXW 800EXW
5500 6000 25800 27600 6700
2650
3300
29500
4200
4400
5100
7200
8500
900EXW 1000EXW 1120EXW 1250EXW 1400EXW 1500EXW 1600EXW 1680EXW 1800EXW 1900EXW 2000EXW
7300 8000 6700 7300 8000 8500
32300 34700 43900 46400 49000 51200
Manufacturer reserves the rights to change specifications without prior notice.
69
9000
3300
3900
53500
9500 10000 10500 11000
55800 58600 61300 64100