YORK ® AIR-CONDITIONING PRODUCTS
Water-cooled magnetic centrifugal chiller
YMC 2 S0800AA to S3600AB
Nominal capacity (*)
YMC 2
Cooling capacity (kW)
EER
SEER
S0800AA
800
6.06
7.58
295
77
ŋs, c
Sound pressure at 1 m (dBA)
YMC 2
Cooling capacity (kW)
EER
Sound pressure at 1 m (dBA)
S2200AB
2200
6.2
81
S1000AA
1000
6.13
7.83
305
77
S2400AB
2400
6.25
82
S1200AB
1200
6.32
7.92
309
76
S2600AB
2600
6.1
82
S1400AA
1400
6.33
8.34
326
76
S2800AB
2800
6.15
82
S1600AB
1600
6.31
8.59
335
77
S3000AB
3000
6.2
82
S1800AB
1800
6.07
7.83
305
79
S3200AB
3200
6.2
82
S2000AB
2000
6
8.16
318
80
S3400AB
3400
6.1
83
S3600AB
3600
6.1
83
Cooling Capacity at Eurovent Conditions, entering/leaving chilled water temperature 12°C/7°C, entering/leaving condenser water temperature 30°C/35°C
(*) YMC 2 is a tailor and tune chiller. Its peformance will be factory-adjusted to match the exact site requirements based on the specific project operating.
The table above shows only a representative sample of performance points based on generic project operating conditions working with R134a refrigerant.
For R513a information contact your JCI Representative.
The above data is based on Johnson Control’s selection software YORKworks 18.06. Please refer to the latest version of the software for specific projects.
Technical data
YMC 2
S0800AA
Length
Dimensions
Width
Height
Shipping weight (kg)
Refrigerant charge (kg)
S1200AB
3048
S1400AA
S1600AB
S2200AB
280
423
S2400AB
mm
mm
mm
S2600AB
454
S2800AB
S3000AB
2573
7809
612
S3200AB
5154
2007
2573
10095
667
10161
666
S2000AB
2007
2499
6579
445
5810
278
S1800AB
4267
1880
2410
5171
YMC 2
Length
Dimensions
Width
Height
Shipping weight (kg)
Refrigerant charge (kg)
S1000AA
mm
mm
mm
656
S3400AB S3600AB
12048
750 12254
750
5054
2235
2656
10255
658
10432
647
11500
766
11669
760
1. All dimensions are approximate. Certified dimensions are available on request.
2. Refrigerant charge quantity and shipping weights will vary based on tube count.
3. Shipping weights are based on fully assembled and charged units.
4. Refer to product drawings for detailed weight information.
Superior sound reduction
OptiView control centre
A-Weighted sound pressure level (dBA (re: 20µPa))
Measured in accordance with AHRI-575
Competitor
YORK ® YMC 2
5 dBA*
% Chiller full load
The OptiView control centre provides complete diagnostics
to speed troubleshooting.
The YMC chiller is so much quieter than competitive magnetic-bearing chillers,
it sounds about half as loud. *Note: each segment on the Y axis = 5 dBA.
2
Manufacturer reserves the rights to change specifications without prior notice.
65