YORK ® AIR-CONDITIONING PRODUCTS
Dimensions and hydraulic connections
Closed-loop configuration models
YVFA 1239 CL
All dimensions in mm. Drawings not a scale.
Application flexibility (*) example of selections
YVFA
Mechanical Cooling capacity (kW)
Full Load Efficiency (EER) - Mechanical
Part Load Efficiency (SEPR) - Mechanical
Sound power level (dBA) - Mechanical
Total Temperature Free-Cooling (°C)
Efficiency during Hybrid Mode
Efficiency during Total Free-Cooling Mode
0539
529
3.03
6.13
103
0.5
8-40
40-115
0709
657
3.00
6.14
104
0.2
6-40
40-125
0889
846
3.05
6.33
106
-0.7
6-35
35-125
1009
946
3.19
6.62
105
-0.5
6-35
35-135
1069
1050
3.07
6.35
106
-1.5
5-28
28-125
1239
1213
2.98
6.01
109
-1.8
5-24
24-125
1419
1378
2.89
6.07
110
-2.1
5-27
27-125
1589
1473
2.84
6.03
110
-2.8
5-28
28-115
Cooling Capacity at: entering/leaving chilled water temperature 15°C/10°C (30% Glycol), ambient temperature 35°C
Sound Pressure according to Eurovent conditions.
(*) YVFA is a tailor and tune chiller. Its peformance will be factory-adjusted to match the exact site requirements based on the specific project operating conditions.
The table above shows only a representative sample of performance points based on generic project operating conditions working with R134a refrigerant.
For R513a information contact your JCI Representative.
For tailored and tuned performance based on your specific project requirements, and for more information, please contact your Johnson Controls representative.
The above data is based on Johnson Control’s selection software YORKworks 18.06. Please refer to the latest version of the software for specific projects.
Technical data
YVFA
Dimensions
Operating weight kg
Refrigerant charge kg
Length
Width
Height
mm
mm
mm
0539
6280
0709
7397
0889
8514
1009
9631 1069
9631 1239
10748 1419
11842
246 11884
262 12900
282 14131
365
2242
2405
7394
172
8504
164
10396
216
45
1589
11864
2243
2404
17140
368