York HVAC Catalogue 2018 EN 2019 EN | Page 27

YORK ® AIR-CONDITIONING PRODUCTS Heat pump scroll compressor YLRA 0200 to 0330 Nominal capacity YLRA BLN versions Cooling capacity (kW) EER SEER 0200 181.3 2.93 4.35 171 200.1 3.22 3.25 127 92 ŋc, h Heating capacity (kW) COP SCOP ŋs, h Sound power level (dBA) 0230 213.6 2.92 4.25 167 229 3.23 3.43 134 92 0260 243.7 2.91 4.225 166 262.3 3.21 3.43 134 93 0280 261.1 2.88 4.225 166 279.6 3.2 3.43 134 93 0300 287.7 2.92 3.95 155 305.6 3.22 3.33 130 94 0330 307.4 2.97 3.925 154 327.2 3.21 3.43 134 95 Net values at Eurovent nominal conditions: Cooling capacities in kW given for 7°C water leaving temperature ∆t 5°C and 35°C ambient temperature Heating capacities in kW given for 45°C water leaving temperature and 7°C ambient temperature Ecodesign figures are calculated following variable outlet approach. SCOP calculated according to EN14825. ηs calculated according to Ecodesign regulation for heating (2016/2281) Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744 and Eurovent 8/1 The above data is based on Johnson Control’s selection software YORKworks 18.06. Please refer to the latest version of the software for specific projects Technical data YLRA BLN versions Dimensions 0200 Length Width Height 0230 mm mm mm Operating weight (kg) 0260 0280 0300 3 500 0330 4 550 2 150 2 600 1858 1993 2216 2226 2806 2899 Operating limits Thanks to the different versions available, the YLRA is working in a wide operating envelope in cooling mode. Special attention to the Polar Version optional, which is extending the heating envelope of the units to allow operation at ambient temperatures as low as -18°C. Operating limits in cooling mode YLRA BLN YLRA SLN Operating limits in heating mode YLRA BLN with EC fans Manufacturer reserves the rights to change specifications without prior notice. 27 Polar Version