YORK ® AIR-CONDITIONING PRODUCTS
Modular screw chillers and heat pumps
YCME/YHME 0162HE to 0222HE
YCME Air-cooled Chiller Performance Data
YCME0162HE YCME0182HE YCME0202HE YCME0222HE
Cooling capacity
Individual modules
kW 159.6 179.6 204.5 224.4
Total power input kW 51.32 57.75 65.34 71.01
SEER 4.11 4.13 4.12 4.12
ŋs, c 161 162 162 162
96 97 98 Sound power level dB(A)
Dimensions (H x W x D) mm
Operating weight kg
Chilled Water Outlet (std, options Low / High) °C
Ambient Air Temperature °C
2450 x 1955 x 2290
1300
99
2450 x 1955 x 3230
1340
1590
1680
+5°C ~ +15°C, with Options -10°C ~ +5°C / +15°C ~ +30°C
-15°C ~ +46°C
Electrical Power Supply
3N - 400V 50Hz
YHME Air-cooled Heat Pump Performance Data
YHME0162HE YHME0182HE YHME0202HE YHME0222HE
Cooling capacity
Individual modules
kW 149.7 169.6 194.6 209.5
Total power input kW 51.09 57.88 65.97 70.3
Heating capacity kW 145.4 145.4 185.5 185.5
Total power input kW 51.56 51.56 65.32 65.32
SCOP
Meet Ecodesign requirements
ŋs, h
Sound power level dB(A) Dimensions (H x W x D) mm Operating weight kg Chilled Water Outlet (std, options Low / High) °C Heated Water Outlet °C +35°C ~ +55°C
Ambient Air Temperature (Cool / Heat) °C -15°C ~ 46°C / -9.5 (DB), -10 (WB) ~ +21 (DB), +15.5 (WB)
96
97
98
2450 x 1955 x 2290
1400
99
2450 x 1955 x 3230
1420
1680
1760
+5°C ~ +15°C, with Options -10°C ~ +5°C / +15°C ~ +30°C
Electrical Power Supply
3N - 400V 50Hz
Net values at Eurovent nominal conditions:
Cooling capacities in kW given for 7°C water leaving temperature ∆t 5°C and 35°C ambient temperature.
Heating capacities in kW given for 45°C water leaving temperature and 7°C ambient temperature.
Ecodesign figures are calculated following variable outlet approach.
For Ecodesign calculations, please contact your JCI representative.
Sound Pressure: measured at 1.5m height, and at 1m distance from the control panel.
The above data is based on Johnson Control’s selection software YORKworks 18.06. Please refer to the latest version of the software for specific projects.
°C
Widest operating range at highest efficiency
+30
YCME/YHME Cooling operating range
Chilled water outlet temperature: -10°C to +30°C
Ambient temperature: -15°C to +46°C
YHME Heating operating range
Hot water outlet temperature: +35°C to +55°C
Ambient temperature: -10°C (WB) to +15.5°C (WB)
Two operating modes selectable at commissioning allow the installation’s
performance to focus on either high efficiency or high accuracy outlet
water temperature.
High water temperature (option)
+15
Standard
+5
Brine
(Low 1 option) (low 2 option)
-5
Brine (Low 3 option under development)
-10
-15
Manufacturer reserves the rights to change specifications without prior notice.
19
Ambient temperature
+46 °C