York HVAC Catalogue 2018 EN 2019 EN | Page 161

YORK ® AIR-CONDITIONING PRODUCTS Horizontal supply Version for in-row installation with front and lateral air supply. Technical Characteristics YC-HRA: direct expansion air conditioners with air-cooled or water-cooled condensers and horizontal air supply Models Total cooling capacity (1) Sensible cooling capacity (1) EER (2) Airflow Sound pressure level (3) Lenght Depth Height Net weight Free Cooling Two Sources kW kW m 3 /h dB(A) mm mm mm kg 231 21.9 21.8 3.52 6.000 52 600 1.222 1.985 215 l l 361 35.1 33.9 3.75 6.800 54 600 1.222 1.985 215 ¡ ¡ YC-HRU: chilled water coil air conditioners with horizontal air supply Models Total cooling capacity (1) Sensible cooling capacity (1) EER (2) Airflow Sound pressure level (3) Lenght Depth Height Net weight Free Cooling Two Sources kW kW m 3 /h dB(A) mm mm mm kg 20 24.1 24.1 18.12 6.000 56 300 1.200 1.970 120 ¡ ¡ 40 36 36 29 9.000 61 600 1.222 1.985 190 l l (1) Performance refers to: R410a refrigerant; condensing temperature 45°C; incoming air 32°C-30%Rh; water 15/20°C; external static pressure 30 Pa. The declared performance does not take into account the heat generated by fans, which must be added to the system thermal load. (2) EER (Energy Efficiency Ratio) = total cooling capacity / compressors power consumption + fans power consumption (air cooled condensers excluded). (3) Sound levels at a 2 m distance, in a free field, as per UNI EN ISO 3744:2010. Manufacturer reserves the rights to change specifications without prior notice. 161