YORK ® AIR-CONDITIONING PRODUCTS
Horizontal supply
Version for in-row installation with front and lateral air supply.
Technical Characteristics
YC-HRA: direct expansion air conditioners with air-cooled or water-cooled condensers and horizontal air supply
Models
Total cooling capacity (1)
Sensible cooling capacity (1)
EER (2)
Airflow
Sound pressure level (3)
Lenght
Depth
Height
Net weight
Free Cooling
Two Sources
kW
kW
m 3 /h
dB(A)
mm
mm
mm
kg
231
21.9
21.8
3.52
6.000
52
600
1.222
1.985
215
l
l
361
35.1
33.9
3.75
6.800
54
600
1.222
1.985
215
¡
¡
YC-HRU: chilled water coil air conditioners with horizontal air supply
Models
Total cooling capacity (1)
Sensible cooling capacity (1)
EER (2)
Airflow
Sound pressure level (3)
Lenght
Depth
Height
Net weight
Free Cooling
Two Sources
kW
kW
m 3 /h
dB(A)
mm
mm
mm
kg
20
24.1
24.1
18.12
6.000
56
300
1.200
1.970
120
¡
¡
40
36
36
29
9.000
61
600
1.222
1.985
190
l
l
(1) Performance refers to: R410a refrigerant; condensing temperature 45°C; incoming air 32°C-30%Rh; water 15/20°C; external static pressure 30 Pa.
The declared performance does not take into account the heat generated by fans, which must be added to the system thermal load.
(2) EER (Energy Efficiency Ratio) = total cooling capacity / compressors power consumption + fans power consumption (air cooled condensers excluded).
(3) Sound levels at a 2 m distance, in a free field, as per UNI EN ISO 3744:2010.
Manufacturer reserves the rights to change specifications without prior notice.