YORK ® AIR-CONDITIONING PRODUCTS
Heat pump scroll compressor
YLRA 0200 to 0330
Nominal capacity
YLRA BLN versions
Cooling capacity (kW)
EER
Heating capacity (kW)
COP
SCOP
0200
182
2.93
200
3.23
3.25
127
92
ŋs, h
Sound power level (dBA)
0230
213
2.92
229
3.23
3.43
134
92
0260
244
2.91
262
3.21
3.43
134
93
0280
261
2.88
279
3.21
3.43
134
93
0300
288
2.92
306
3.22
3.33
130
94
0330
309
2.97
328
3.21
3.43
134
95
Net values at Eurovent nominal conditions:
Cooling capacities in kW given for 7°C water leaving temperature ∆t 5°C and 35°C ambient temperature
Heating capacities in kW given for 45°C water leaving temperature and 7°C ambient temperature
SCOP calculated according to EN14825
ηs calculated according to Ecodesign regulation for heating (2016/2281)
Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744 and Eurovent 8/1
The above data is based on Johnson Control’s selection software YORKworks 17.06. Please refer to the latest version of the software for specific projects
Technical data
YLRA BLN versions
Dimensions
0200
Length
Width
Height
0230
mm
mm
mm
Operating weight (kg)
0260
0280
0300
3 500
0330
4 550
2 150
2 600
1858
1993
2216
2226
2806
2899
Operating limits
Thanks to the different versions available, the YLRA is working in a wide operating envelope in cooling mode. Special attention to the Polar Version
optional, which is extending the heating envelope of the units to allow operation at ambient temperatures as low as -18°C.
Operating limits in cooling mode
YLRA BLN
YLRA SLN
Operating limits in heating mode
YLRA BLN with EC fans
Manufacturer reserves the rights to change specifications without prior notice.
29
Polar Version