York HVAC Catalogue 2018 EN 2018 | Page 28

YORK ® AIR-CONDITIONING PRODUCTS Heat pump scroll compressor YLRA 0200 to 0330 Nominal capacity YLRA BLN versions Cooling capacity (kW) EER Heating capacity (kW) COP SCOP 0200 182 2.93 200 3.23 3.25 127 92 ŋs, h Sound power level (dBA) 0230 213 2.92 229 3.23 3.43 134 92 0260 244 2.91 262 3.21 3.43 134 93 0280 261 2.88 279 3.21 3.43 134 93 0300 288 2.92 306 3.22 3.33 130 94 0330 309 2.97 328 3.21 3.43 134 95 Net values at Eurovent nominal conditions: Cooling capacities in kW given for 7°C water leaving temperature ∆t 5°C and 35°C ambient temperature Heating capacities in kW given for 45°C water leaving temperature and 7°C ambient temperature SCOP calculated according to EN14825 ηs calculated according to Ecodesign regulation for heating (2016/2281) Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744 and Eurovent 8/1 The above data is based on Johnson Control’s selection software YORKworks 17.06. Please refer to the latest version of the software for specific projects Technical data YLRA BLN versions Dimensions 0200 Length Width Height 0230 mm mm mm Operating weight (kg) 0260 0280 0300 3 500 0330 4 550 2 150 2 600 1858 1993 2216 2226 2806 2899 Operating limits Thanks to the different versions available, the YLRA is working in a wide operating envelope in cooling mode. Special attention to the Polar Version optional, which is extending the heating envelope of the units to allow operation at ambient temperatures as low as -18°C. Operating limits in cooling mode YLRA BLN YLRA SLN Operating limits in heating mode YLRA BLN with EC fans Manufacturer reserves the rights to change specifications without prior notice. 29 Polar Version