30XAS
Physical data
30XAS
Air conditioning application as per EN14511-3: 2013
Nominal cooling capacity, unit with option 279*
Unit with options 279 and 119**
EER, unit with option 279
EER, unit with options 279 and 119
Eurovent class, unit with option 279
Eurovent class, unit with options 279 and 119
ESEER, unit with option 279
ESEER, unit with options 279 and 119
Operating weight***
Unit with options 279 and 119
Compressor
Refrigerant
Capacity control
Condensers
Condenser fans
Unit with options 279 and 119
Quantity
242
kW
kW
kW/kW
kW/kW
kW/kW
kg
282
342
442
482
232
245
2.76
2.97
C
B
3.78
3.69
284
285
3.00
3.15
B
A
3.93
3.69
334
345
3.08
3.24
B
A
3.99
3.80
430
461
2.93
3.15
B
A
3.87
3.75
467
486
2.87
3.09
C
B
3.96
3.79
2390
2810
06T semi-hermetic screw compressor, 50 r/s
R-134a, one refrigerant circuit
PRO-DIALOG+, electronic expansion valve (EXV)
All aluminium micro-channel heat exchanger
Axial Flying Bird IV fans with rotating shroud
2870
3630
3720
4
6
7
8
20500/27083
23917/31597
27333/ 36111
5
Total air flow, unit with option 279/unit with options 279 and 119 l/s
13667/18055
17083/22569
Flooded shell-and-tube type
Evaporator
Colour code: RAL7035
Chassis paint colour
Dimensions
Length x depth x height
mm
2410 x 2253 x 2297
3604 x 2253 x 2297
NOTE: For the conditions please refer to page 31.
*
Option 279 = compressor enclosure
** Option 119 = high energy efficiency.
*** Weights are guidelines only. The refrigerant charge is also given on the unit nameplate.
4798 x 2253 x 2297
Electrical data
30XAS
242
282
Power circuit
Nominal power supply
V-ph-Hz
400-3-50 ± 10%
24 V via internal transformer
Control circuit
A
303
388
Start-up current*
Unit with options 279 and 119
kW
101/105
113/118
Maximum power input**
A
165/172
185/194
Maximum current draw (Un)**
*
Instantaneous start-up current (locked rotor current in star connection of the compressor).
** Values obtained at operation with maximum unit power input. Values given on the unit name plate.
342
442
482
388
587
587
134/139
218/229
184/190
305/318
213/221
353/368
Note: Motor and fan electrical data if the unit operates at Eurovent conditions (motor ambient temperature 50°C): 1.9 A, start-up current: 8.4 A, power input: 760 W.
Operating range
High energy efficiency unit or option 119
Entering air temperature, °C
Entering air temperature, °C
Standard unit
Evaporator leaving water temperature, °C
Evaporator leaving water temperature, °C
Legend
Operating range, unirt equipped with option 28 "Winter operation"
Below 0°C air temperature the unit must either be equipped with the evaporator frost
protection option (41A or 41B), or the water loop must be protected against frost by using a
frost protection solution (by the installer).
Part load average
49