33-1197 Solahart Owner‟s Manual – Thermosiphon Systems - Revision H – Nov 2013 22 CLOSED CIRCUIT COMMISSIONING PROCEDURE – GENERAL Remove the Fill Plug from the Collector Fill Assembly. Remove PR6/PR200 Valve from the Tank. Connect a ½” hose to the Collector Fill Assembly and fill the Closed Circuit with water. (Hose to be supplied by Installer). 1 Continue filling until water overflows from the Jacket Relief Valve Port and there are no air bubbles in the overflowing water. 2 Fit the Test Block into the Jacket Relief Valve Port. 3 Fit the PR6/PR200 Valve to the Test Block. 4 Remove the hose from the Collector Fill Assembly and replace the Fill Plug as quickly as possible to minimise fluid spillage. 5 IMPORTANT: If more than 0.5 litres of fluid is spilled, repeat steps 1-5 When charging the system using a PR200 Valve, pressurise the system until the PR200 Valve opens or until a pressure of 170kPa is read on the pressure gauge, whichever happens first. When charging the system using a PR6 Valve, pressurise the system until the PR6 Valve opens or until a pressure of 80kPa is read on the pressure gauge, whichever happens first. Connect a bicycle pump/portable compressor to the Test Block and pressurise the Closed Circuit to 80kPa/170kPa, as appropriate. Remove bicycle pump/portable compressor from Test Block. ! 6 WARNING: DO NOT ALLOW THE CLOSED CIRCUIT PRESSURE TO RISE ABOVE 200KPA OR PERMANENT SYSTEM DAMAGE MAY OCCUR. If the PR6/PR200 Valve opens during the pressure test, wait until the Valve re-seals before checking all connections for evidence of leakage. If the Valve does not open during the pressure test then check all connections for any evidence of leakage. 7 Ensure that the Closed Circuit pressure remains stable for at least 10 minutes. 8 If any leakage is observed at any of the connections, rectify the problem and repeat steps 1 to 8. Release the pressure from the Closed Circuit by removing the PR6/PR200 Valve from the Test Block. Once the pressure is relieved, replace PR6/PR200 Valve. 9 Remove the Fill Plug from the Fill Assembly and connect the ½” hose as quickly as possible to minimise fluid spillage. 10 11