All penetrations must be sealed using approved materials rated for the application = S . T . I . Fire Caulk
Must be completed in a manner consistent with U . L . requirements
Must not exceed 30 % fill on most EMT penetrations - this is generally the maximum !
No fire caulking , putty or other sealant may be removed . All new low voltage penetrations will utilize the E-Z Path