24 www. refrigerationandaircon. co. za RACA Journal I November 2026
HUMIDIFICATION feature

HUMIDITY CONTROL MOVES BEYOND THE THERMOSTAT

By Ian MacDonald and Nancy Strangfeld( Data Centre Solutions( Pty) Ltd)
Humidity is often treated as a secondary consideration in HVAC design, with temperature receiving most of the attention. Yet moisture content can have a profound effect on indoor air quality, occupant comfort, product quality, process reliability, building integrity and even equipment performance.

In South Africa, the requirements can vary considerably. Coastal areas such as Durban, Cape Town and parts of the Eastern Cape can experience persistently high humidity, while the Highveld can become extremely dry during winter. Beyond general comfort, healthcare, pharmaceutical, food processing, cold-chain, industrial and other controlled environments can have much more demanding requirements.

According to Christiaan Schalekamp, managing director of Condair Southern Africa, and Andries Bekker, Eco Solutions sales head at LG Electronics South Africa, humidity needs to be considered alongside temperature rather than treated as an afterthought.
“ Humidity is often the forgotten component of indoor environmental quality. While most people focus on temperature, excessive moisture in the air can significantly affect comfort, health, building integrity and energy consumption,” Bekker says.
Schalekamp points out that moisture content can similarly affect product quality, process reliability and equipment performance. Effective humidity control therefore begins with understanding the application rather than selecting equipment first.
HUMIDITY IS NOT ALWAYS VISIBLE One of the challenges with excessive indoor humidity is that occupants may not recognise it as the underlying cause of a problem. Condensation on windows, musty odours, mould growth, damp clothing and general discomfort can all be indications of excessive moisture. Yet many simply live with these conditions without understanding that humidity can negatively affect their wellbeing, belongings and homes.
“ Awareness of temperature control is relatively high, but awareness of humidity control remains limited,” Bekker says. For HVAC & R engineers, however, humidity is a measurable design parameter. Psychrometrics – the relationship between temperature, relative humidity, moisture content, dew point and enthalpy – remains fundamental to effective humidity control.
Dew point is particularly useful because it provides a direct indication of the moisture content of air and helps engineers determine when condensation may occur. Correct measurement and control of these parameters are fundamental to designing systems capable of maintaining both temperature and relative humidity within the required limits.
This makes the selection and positioning of humidity sensors important, as is proper commissioning of the control system. Humidity control is not simply about removing moisture. Depending on the application, the challenge may be to add moisture to excessively dry air. The appropriate humidification technology depends on the required accuracy, hygiene requirements, water quality, available energy and the tolerance of the space to variations in relative humidity.
Steam remains the preferred approach where tight, repeatable control and hygiene are critical, such as pharmaceutical cleanrooms and healthcare applications.
Evaporative and adiabatic systems can be attractive for larger spaces where wider control bands are acceptable and where the associated evaporative cooling is beneficial. High-pressure fogging, for example, can be particularly effective in horticultural applications where both humidity and cooling are required, while in-duct adiabatic humidification can make sense in large printing or paper-processing facilities.
Ultrasonic and hybrid systems also have a role, particularly where low energy consumption, compact equipment or specific application requirements influence the design. Schalekamp says:“ There is no universally‘ best’ humidification technology. The correct choice is the one that provides the required control at an acceptable capital and lifecycle cost.”
WATER QUALITY MATTERS For humidification systems, water quality is an important part of the design, particularly in South Africa. Schalekamp explains that water hardness varies considerably between regions, while mining and rural industrial sites may rely on borehole water of variable quality. This can affect scaling, maintenance and hygiene.
Electrode steam humidifiers with disposable cylinders can be advantageous in harder-water areas, while high-pressure and adiabatic systems generally require appropriate water treatment, including reverse osmosis where necessary.
In food and beverage applications, water treatment may already be required to meet process and potable water requirements.“ Water treatment should therefore be addressed during specification rather than treated as an afterthought,” Schalekamp says.
Where excessive moisture is the problem, dehumidification becomes necessary. Ventilation is often the first line of defence, but it is not always effective in humid climates where outdoor air already contains high moisture levels. Air conditioning can also assist with reducing humidity, although many South African homes do not have air conditioners installed. Fixed airconditioning systems also typically serve specific rooms.
A dedicated dehumidifier can provide a more flexible solution in such situations. A portable unit can be moved between rooms and is designed specifically to remove moisture from the air without significantly affecting room temperature.

24 www. refrigerationandaircon. co. za RACA Journal I November 2026