Corrosion of the enclosure plates – right hand side .
Macro-image – sample A location 2 , 3x magnification .
The microstructure of the copper tubing was consistent with copper ; however , inconsistent grain sizes indicate that improper heat input may have been present during the fabrication / joining process . RACA
“ From visual inspection , it was evident that the entire heat exchanger was subject to corrosive attack .”
Corrosion of copper pipes at welded components .
Corrosion of the enclosure plates – left hand side .
within the environment in which it was operating . It was also noted that the quality of the joints in the copper tubing was inconsistent . The copper tubes were confirmed to have corroded prior to the epoxy putty repair , with sections of the paint layer not providing sufficient corrosion protection .