RACA Journal June 2019 | Page 58

Support CALCULATION OF LOW PRESSURE SWITCH SETTING 5 CUT- IN = 236.5 kPa BT = 3˚C (Automatic Defrost Required) TD = 9K ET = 6˚C = 132.9 kPa COP = Cut out Pressure CIP = Cut in Pressure PD = Pressure Drop (21 kPa) (General rule) MSP = Minimum Suction Pressure (14 kPa) Cut out Pressure: COP = ET - MSP - PD COP = 132.9 - 14 - 21 kPa COP = 97.9 kPa Cut in Pressure 1 AVERAGE SUCTION PRESSURE (Compressor runnning ½ way into cycle) 4 PRESSURE DROP IN COIL 3 MINIMUM SUCTION PRESSURE 2 CUT OUT POINT = 132,9 kPa CIP = BT +1˚C CIP = 3˚C + 1˚C CIP = 4˚C (Convert to kPa) CIP = 236,5 kPa = 21 kPa =14 kPa = 97,9 kPa Calculation of low-pressure switch settings in practice 56 RACA Journal I June 2019 www.hvacronline.co.za