RACA Journal January 2020 | Page 71

Support superheat even when there is proper subcooling. In some cases, it’s not possible to achieve the required subcooling without having a superheat of zero degrees. If there is zero degrees superheat with a TEV, then the TEV is defective and will need to be replaced. CHARGING BY MASS I would be remiss not to mention the method of charging according to mass. This method, known as the weigh in method, can be very accurate if the exact length of the refrigerant lines is known. The outdoor unit usually comes pre-charged with enough refrigerant for the outdoor unit, a standard indoor unit, and 3 – 6 metres of line set. Refrigerant must be added for any line length over what is specified by the manufacturer. Refrigerant may also have to be added or removed depending on what indoor unit or indoor coil is used. When charging by weigh in, it’s still good practice to check the charge using the subcooling or superheat methods to ensure correct operation. DIAGNOSIS Data from superheat and subcooling measurements can be used to determine various conditions within the system, including checking the refrigerant charge and verifying the operating condition of the metering device. These measurements can also be used to determine the efficiency of the condenser, evaporator, and compressor. Before drawing conclusions from the measured data, it is important to check external conditions that influence system performance. In particular, inspection and verification of proper airflow across coil surfaces. Remember to look for obvious problems at the coil surfaces, such as dirty air filters inside the unit, or leaves and debris restricting airflow on the condenser. The superheat value can indicate various system problems, including a clogged filter-drier, refrigerant undercharge, overcharge, faulty metering device, restricted airflow, or improper fan motor or blower direction. Suction line superheat is a good place to start diagnosis; a low reading suggests that liquid refrigerant may be reaching the compressor. In normal operation on traditional systems, which use mechanical metering devices such as TEVs or capillary tubes, refrigerant entering the compressor is sufficiently superheated above the evaporator boiling temperature to ensure that the compressor draws only vapour and no liquid refrigerant. On systems that use electronic expansion valves and solid-state controllers, it is possible to see the superheat setting as low as three degrees. A low or zero superheat reading indicates that the refrigerant did not pick up enough heat in the evaporator to completely boil into a vapour. Liquid refrigerant drawn into the compressor typically causes slugging, which can damage the compressor valves and/or internal mechanical components. Additionally, liquid refrigerant in the compressor, when mixed with oil, reduces lubrication and increases wear, which leads to premature failure. www.hvacronline.co.za System showing subcooling. On the other hand, if the superheat reading is excessive, it indicates that the refrigerant has picked up more heat than normal, or that the evaporator is being starved of refrigerant. Possible causes include a metering device that is underfeeding, improperly adjusted, or faulty. Any additional problems with high superheat could indicate a system undercharge, refrigerant restriction, moisture in the system, blocked filter-drier, or excessive evaporator heat loads. USING SUBCOOLING FOR TROUBLESHOOTING Refrigerant is usually subcooled towards the outlet of the condenser. An improper subcooling value can indicate various system problems, including overcharge, undercharge, liquid line restriction, or insufficient condenser airflow (or water flow when using water- cooled condensers). For example, a very low reading indicates that the refrigerant did not lose the normal amount of heat in its travels through the condenser. Possible causes for this condition include insufficient airflow over the condenser where the problem may be simply that the condenser coil surface needs to be cleaned thoroughly to eliminate airflow restriction. This shows how measurement of the subcooling in the system will indicate possible issues in the system. Excessive subcooling (over condensing) means the refrigerant has been cooled more than normal. A possible explanation is faulty head pressure control during low ambient conditions. Karel, I hope that this assists you with a better understanding of subcooling in the refrigeration system which is critical knowledge we should all have. REFERENCES: ACRA RACA Thank you for all your questions. Send your problems (and sometimes your creative solutions) to [email protected] with ‘Solutions Page’ in the subject line. You may include pictures. RACA Journal I January 2020 69