Project |
• A minimum of 6 air changes per hour ( ACH ) is provided into |
|||||||
the spaces . |
|||||||
• Standalone extract system will serve each area enabling the |
|||||||
The theatre plantroom . |
© RACA Journal | Benjamin Brits |
ward / department to be under negative pressure . º Extract grilles will be placed at the furthest point from the entrance door in order to create the required pressure cascading / air flow direction .
Typical schematic of airflow during Normal and Pandemic modes is shown below :
|
|||||
Internal view - AHU ( fan and LEV kits ). |
© RACA Journal | Benjamin Brits |
Figure 1 : normal mode . |
© Spoormaker and Partners |
||||
One of the fresh air intakes for the main plantroom located on the roof . |
© RACA Journal | Benjamin Brits |
Figure 2 : pandemic mode . |
© Spoormaker and Partners |
||||