RACA Journal April 2020 | Page 58

Getting Technical gravity which resulted in sufficient water pressures at lower levels in the building but reduced pressures at higher levels causing low flow rates. Even worse were water flows from the holding tanks to cooling towers and other machinery mounted on the roof at the same level. Provided that the water level in the tank did not drop more than about halfway (50% of tank capacity), cooling towers and humidifiers could run under normal loading conditions. However, unexpectedly high ambient conditions or even relatively small leaks in water circulating systems could raise demand from the tank to greater than the low-pressure supply capability which often ended up in system failures through trip-outs. Discomfort caused by air conditioning plant trip-outs tended to draw attention away from higher expenses and energy losses inherent in additional plant restarts. In general, electrical power for refrigerant compressors, water pumps and axial or centrifugal air moving fans was a minor initial design consideration with little or no consideration of unexpected energy costs during operation from commissioning through whatever periods it was expected (or hoped) that the plants involved would continue to run reliably. Another of the most common potential problem points in water circuits, including circuits in HVAC installations, up until around the end of the 1980s was ‘dead ends’ where the flanged ends of water pipes were blanked off for future plant expansions. These dead ends were only small volumes but the water in them 56 RACA Journal I April 2020 became rapidly stagnant and de-oxygenated resulting in growth of acid-producing anaerobic bacteria which spread throughout the water circuits causing corrosion. Some of the blanked off pipes were fairly large, between 250 and 350mm in diameter. However, it was normally relatively easy to weld small valved fittings onto the flange blanks, drill through the blanks and connect 6mm tubing from the fitting to the inlet sides of nearby circulating water pumps – or other lower pressure points of re-entry into the circuit. The small amount of water flow through the 6mm tube was sufficient to eliminate the “dead end” situation and had no measurable impact on design circuit water flow rates. ‘Dead ends’ are seldom seen today but new potential problem points arise for which mechanical modifications which may seem expensive initially are often the optimum solution choices. Water circuits supplied with softened water usually require little or no bleed-off. Drift and spray losses from evaporative cooling towers supplemented by low flow rate continuous trickle drains provided enough bleed-off to prevent cycles of concentration rising too rapidly between regular draining of cooling tower sumps which tended to be done as frequently as needed without any regard to the accompanying increases in fresh water and treatment chemical usages. Only very few people seemed to perceive the situation as being too good to last! It was. www.hvacronline.co.za