Protection Engineering Basics and Schemes Protection Engineering | Page 74
Interconnection of relays and panels is done by about
6sqmm low voltage insulated wires as modern relays are
low voltage operated with very low burden.
i am taking one example for capacitor panel protection
engineering drawing , and we will try to understand it
what that drawing informing us.
in all drawings , they 1st give you contents of drawing
then legends , but remember some legends must be on
engineer finger tips , K symbol is universally accepted for
auxiliary relays, remember auxiliary relays are relays
used for circuit isolation, multiple contacts and indication
purposes . Q symbol is for Breaker, Relays will be shown
by their ANSII numbers like
pg. 74
51 for OC
51N for Earth Fault overcurrent Relay
64G for ground Detector relay
74 for trip circuit supervision relay