Protection Engineering Basics and Schemes Protection Engineering | Page 248

Chapter 8 Auto reclosure As per one estimate approximately 85% of faults occurs in power system is transient or temporary in nature. If we consider time than in any system there are three types of faults  Transient  Permanent  Semi-permanent In my past organization we monthly has 156 tripping on 24 Feeder, when we traced the cause of faults many are like that  Bird burnt out  Tree branch touched overhead conductors due to fast wind Out of 156 tripping, we found 94% tripping is transient in nature means no fault found after complete feeder inspection. Due to absence of transient fault mitigation we lost 1. Approximately 200 man hour pg. 248