Protection Engineering Basics and Schemes Protection Engineering | Page 200

Due to different CT ratio on both side of transformer we used Interposing CT; interposing CT corrects ratio and Phase errors. Matching factor is term used for different ratio CTs currents comparison in differential protection for transformer. 6.3.1.1 Differential Relays application: First application we will discuss is busbar Differential protection. Rule is same, current in to feeder from source is equal to current exist from feeder to load on bus. pg. 200