Protection Engineering Basics and Schemes Protection Engineering | Page 20

      pg. 20 you are the person removing cover you can be acted as earth. Check Voltage on all secondary output from Test block, it must be zero. Then take CT one of contact you need to test, the other contact is the return path or star point if you have CT connected in star. Now your CT is in Dead state , place your ammeter in series and voltmeter in parallel with your at test CT connection, Complete your connection by connecting them with power supply of 250V (from variable Transformer- VARIAC) and have capability of injecting 8A current in circuit. Now start raising voltage slowly and kept eyes on Voltmeter and ammeter, the point at which you observe the slight raise in voltage will result in spike in current value, note that voltage is knee point voltage. After conducting test and note values , reduce voltage to zero level and observe current at zero value then wait for some time , make this duration more when you are conducting test on remnant flux CTs(TCX,TCY and TCZ) In case of any CT with 1A secondary current , we must use one step transformer with our VARIAC,