Protection Engineering Basics and Schemes Protection Engineering | Page 16

1.1.5 CT types as per applications: When we are dealing with errors in CT we combined both phase displacement and ratio error in composite error , We subdivided our CTs in classes as per their composite errors and with respect to their application. Protection CTs Classes  5P  10P Metering CTs Classes  0.1  0.2  0.5  1  3  5 1.1.6 Accuracy limit Factor: Accuracy limit factor is the ratio of maximum primary current CT can bear without exceeding errors defined in class to rated primary current pg. 16