1.1.5 CT types as per applications:
When we are dealing with errors in CT we combined both
phase displacement and ratio error in composite error ,
We subdivided our CTs in classes as per their composite
errors and with respect to their application.
Protection CTs Classes
5P
10P
Metering CTs Classes
0.1
0.2
0.5
1
3
5
1.1.6 Accuracy limit Factor:
Accuracy limit factor is the ratio of maximum primary
current CT can bear without exceeding errors defined in
class to rated primary current