Protection Engineering Basics and Schemes Protection Engineering | Page 125

The contact of directional and overcurrent relay are in series, at time of fault-forward (when current at secondary circuit of CT is exceed from the Pick up value (PSM)). The breaker trip coil energizes and got trip. If the relay construction is electromagnetic In it there are two coils on stator, one is current coil and voltage coil and there is rotating disc, Our reference here is Voltage And current is and like watt hour meter, the torque in rotating disc is; When fault is at point P1 (figure 1), the current is lagging voltage by 90 degree and torque is maximum, means disc rotate with maximum torque and Energized relay tripped circuit breaker. T=KVA cos (90-90) = KVA cos 0= KVA pg. 125