Protection Engineering Basics and Schemes Protection Engineering | Page 120

3phase short circuit current level , one example of such settings are given below Section Rating (MVA) Short circuit MVA Power Grid Transfor mer 1- 33KV Transfor mer 1- 11KV Transfor mer 2- 11KV Voltage level (KV) Full load current(Ir ) Short Circuit Current 20 117.647 0588 33 349.9195 185 2058.350 109 10 142.857 1429 33 174.9597 593 2499.425 132 10 142.857 1429 11 524.8792 778 7498.275 397 1 17.3913 0435 11 52.48792 778 912.8335 265 Pick up 1.15 044 2 1.18 181 8 1.18 181 8 1.18 181 8 Instant aneou s Setting (8*Pic k up) 9.2035 39823 9.4545 45455 9.4545 45455 9.4545 45455 Earth Fault Pick up 1.017 69911 5 1.045 45454 5 1.045 45454 5 1.045 45454 5 Instant aneou s Earth Fault Pick up 8.1415 9292 8.3636 36364 8.3636 36364 8.3636 36364 Another example, Feede r Name Statu s State XXYY Singl e Cable pg. 120 Feede r Hits at Feede r Hits IN Type of Relay CT Ratio S/S State XXYY CDG 31 400/ 5 Relay Protectio n A (O/C) E/F C (O/C) Pick- Curren up t curren setting t A A 2.5 1 2.5 Plug setting multiplay er (P.S.M) Time- setting multipli er 0.2 0.1 0.2