PROFIS Design Guide: US-EN Summer 2021 | Page 87

PART 3 TENSION LOAD

Pullout Failure Mode
Variables f ́c
Variables ACI 318-14 Chapter 17 Provision Comments for PROFIS Engineering
f ́c 17.4.3.4 The pullout strength in tension of a single headed stud or headed bolt , N p , for use in Eq .
( 17.4.3.1 ), shall not exceed
N p
= 8A brg f ́c ( 17.4.3.4 ) f ́c is a parameter used to define concrete compressive strength . This parameter is used to calculate the “ pullout strength in tension for a single anchor ” ( N p
) per Eq .
( 17.4.3.4 ) for cast-in anchors , and the nominal pullout strength ( N p , f ́c ) per ICC-ESR provisions for post-installed mechanical anchors .
17.2.7 The values of f ́c used for calculation purposes in this chapter shall not exceed 10,000 psi for cast-in anchors , and 8000 psi for post-installed anchors . Testing is required for post-installed anchors when used in concrete with f ́c greater than 8000 psi .
Excerpt from ICC-ESR-1917 for the Hilti Kwik Bolt-TZ ( KB-TZ ) expansion anchor referencing provisions for pullout strength in tension .
4.1.4 Requirements for Static Pullout Strength in Tension : The nominal pullout strength of a single anchor in accordance with ACI 318-14 17.4.3.1 and 17.4.3.2 or ACI 318-11 D . 5.3.1 and D . 5.3.2 , respectively , as applicable , in cracked and uncracked concrete ,
N p , cr and N p , uncr , respectively , is given in Tables 3 and 4 . For all design cases , ψ c , p
= 1.0 . In accordance with ACI 318-14 17.4.3 or ACI 318-11 D . 5.3 , as applicable , the nominal pullout strength in cracked concrete may be calculated in accordance with the following equation :
N p , f ́c
= N p , cr f ́c ( Eq-1 ) 2500
In regions where analysis indicates no cracking in accordance with ACI 318-14 17.4.3.6 or ACI 318-11 D . 5.3.6 , as applicable , the nominal pullout strength in tension may be calculated in accordance with the following equation :
N p , f ́c
= N p , uncr f ́c ( Eq-2 ) 2500
Post-installed mechanical anchors can be shown compliance under the International Building Code via testing per the ICC-ES acceptance criteria AC193 in conjunction with the ACI standard ACI 355.2 . f ́c provisions for a specific postinstalled anchor are derived from this testing and will be given in the ICC-ESR for the anchor . PROFIS Engineering uses these f ́c provisions for post-installed anchor design . The post-installed anchor portfolio in PROFIS Engineering is limited to installation in concrete having a specified compressive strength between 2500 psi and 8500 psi , and design using an f ́c-value less than or equal to 8000 psi . Reference the ICC-ESR for f ́c information specific to a post-installed anchor .
PROFIS Engineering users can input an f ́c-value within the range 2500 psi < f ́c < 8500 psi for post-installed anchor design . The maximum f ́c-value for calculations will be limited to 8000 psi .
PROFIS Engineering users can input an f ́c-value within the range 2500 psi < f ́c < 10,000 psi for cast-in anchor design . The maximum f ́c-value for calculations will be limited to 10,000 psi .
Reference the Equations and Calculations sections of the PROFIS Engineering cast-in anchor report for more information on the parameter N p
.
Reference the Equations and Calculations sections of the PROFIS Engineering mechanical anchor report for more information on the parameter N pn , f ́c
. The
PROFIS Engineering report designates the ICC-ESR parameter ” N p , f ́c ” as “ N pn , f c
”.
Where values for N p , cr or N p , uncr are not provided in Table 3 or Table 4 , the pullout strength in tension need not be evaluated .
Reference the Variables section of the PROFIS Engineering mechanical anchor report for more information on the parameter ( f ́c / 2500 ) 0 . 5 .
Excerpt from ICC-ESR-1917 showing values for N p , cr and N p , uncr derived from testing in 2500 psi concrete per AC193 / ACI 355.2 .
ICC-ESR-1917 Table 3
DESIGN INFORMATION
Effective min . embedment
Pullout strength cracked concrete
Pullout strength uncracked concrete
Nominal anchor diameter ( in .)
Symbol
Units
3 / 8
1 / 2
5 / 8
3 / 4
h ef
in .
1-1 / 2
2
2-3 / 4
2
3-1 / 4
3-1 / 8
4
3-1 / 4
3-3 / 4
4-3 / 4
n p , uncr
lb
2160
2515
4110
NA
5515
NA
9145
NA
8280 10680
N p , cr
lb
NA
2270
3160
NA
4915
NA
NA
87 NORTH AMERICAN PROFIS ENGINEERING ANCHORING TO CONCRETE DESIGN GUIDE — ACI 318-14 Provisions