PROFIS Design Guide: US-EN Summer 2021 | Page 95

PART 3 TENSION LOAD

Pullout Failure Mode
Results N pn
Results ACI 318-14 Chapter 17 Provision Comments for PROFIS Engineering HIT-Z anchor with HIT-HY 200
N pn
= N p λ a
17.4.3.1 The nominal pullout strength of a single cast-in , post-installed expansion , and postinstalled undercut anchor in tension , N pn
, shall not exceed
N pn
= ψ c , p
N p
( 17.4.3.1 ) 17.4.3 . 2 For post-installed expansion and undercut anchors , the values of N p shall be based on the 5 percent fractile of results of tests performed and evaluated according to ACI 355.2 . It is not permissible to calculate the pullout strength in tension for such anchors .
Excerpt from ICC-ESR-3187 for Hilti HIT-HY 200 adhesive , referencing provisions for calculating nominal pullout strength in tension ( N pn
) per ACI 318-14 Eq . ( 17.4.3.1 ) with HIT-Z ( carbon steel ) or
HIT-Z-R ( stainless steel ) threaded rods .
4.1.4.1 Static Pullout Strength in Tension : Hilti HIT-Z and HIT-Z-R Anchor Rods : The nominal static pullout strength of a single anchor in accordance with ACI 318-14 17.4.3.1 and 17.4.3.2 or ACI 318-11 D . 5.3.1 and D . 5.3.2 , as applicable , in cracked and uncracked concrete , N p , cr and N p , uncr , respectively , is given in Table 10 . For all design cases , ψ c , p
= 1.0 . Excerpt from ICC-ESR-3187 Table 10 showing values for N p , cr and N p , uncr derived from testing per
AC308 / ACI 355.4 .
ICC-ESR-3187 Table 10
DESIGN INFORMATION Symbol Units
Temperature Range A
Nominal rod diameter ( in .) 3 / 8 1 / 2 5 / 8 3 / 4
Pullout strength in cracked concrete N p , cr lb 7,952 10,936 21,392 27,930
Pullout strength in uncracked concrete N p , uncr lb 7,952 11,719 21,931 28,460
PROFIS Engineering calculates nominal pullout strength in tension ( N pn
) per ACI 318-14 Eq . ( 17.4.3.1 ). Although not referenced in ACI 318-14 Section 17.4.3.2 , pullout failure in lieu of bond failure must be considered for Hilti HIT-HY 200 used with HIT-Z ( carbon steel ) or HIT-Z-R ( stainless steel ) threaded rods . A characteristic pullout strength in tension ( N p
) derived from testing is used to calculate a nominal pullout strength ( N pn ) for HIT-HY 200 when used with HIT-Z / Z-R threaded rods .
The parameter ψ c , p in Eq . ( 17.4.3.1 ) is a modification factor for cracked or uncracked concrete . PROFIS Engineering always uses ψ c , p
= 1.0 for HY 200 / HIT-Z N pn calculations because cracked and uncracked concrete conditions are accounted for in the N p
-values derived from testing . PROFIS Engineering applies a lightweight concrete modification factor ( λ a
), and a seismic modification factor ( α N , seis ), to the N pn
-value if lightweight concrete and / or seismic conditions are being modeled . λ a -values and α N , seis
-values are shown in the
Variables section of the report . PROFIS Engineering uses the N p
-values given in ICC-ESR-3187 Table 10 to calculate a nominal pullout strength for HIT-Z and HIT-Z-R threaded rods used with HIT-HY 200 adhesive . These values are derived from testing per the ICC-ES acceptance criteria AC308 in conjunction with the ACI standard ACI 355.4 . They are specific to either cracked or uncracked concrete for a given anchor diameter , and are valid for concrete compressive strengths
2500 psi < f ́c < 8000 psi .
Reference the Variables section of the report for more information on the following parameters :
• N p
— tested pullout value from ICC-ESR-3187
• λ a
— lightweight concrete modification factor
• α N , seis
— seismic modification factor
Reference the Equations section of the report for more information on the parameter N pn
.
When modeling cast-in anchors , PROFIS Engineering calculates the nominal pullout strength in tension ( N pn
) per ACI 318-14 Eq . ( 17.4.3.1 ), and the parameter N p per ACI 318-14 Eq . ( 17.4.3.4 ). Reference the cast-in anchor report sections relevant to pullout strength in tension for more information .
95 NORTH AMERICAN PROFIS ENGINEERING ANCHORING TO CONCRETE DESIGN GUIDE — ACI 318-14 Provisions