PROFIS Design Guide: US-EN Summer 2021 | Page 71

PART 3 TENSION LOAD

Concrete Breakout Failure Mode
Calculations ψ cp , N
Calculations ACI 318-14 Chapter 17 Provision Comments for PROFIS Engineering
ψ cp , N
= MAX
c a , min , 1.5h ef ≤1 . 0
c ac
c ac
17.4 . 2.7 The modification factor for post-installed anchors designed for uncracked concrete in accordance with 17.4 . 2.6 without supplementary reinforcement to control splitting , ψ cp , N
, shall be calculated as follows using the critical distance c ac as defined in 17.7.6
If c a , min ≥ 1.5c ac
, then ψ cp , N = 1.0 ( 17.4.2.7a )
If c a , min < c ac
, then ψ cp , N = c a , min
( 17.4.2.7b ) c ac
ψ cp , N is a modification factor that considers splitting failure when calculating the nominal concrete breakout strength in tension ( N cb or N cbg ) for a post-installed anchor . The parameter ψ cp , N is only considered when designing post-installed mechanical or adhesive anchors installed in uncracked concrete . Splitting failure will typically not occur for cast-in-place anchors ; therefore , ψ cp , N is always shown equal to 1.0 in PROFIS Engineering when modeling cast-in-place anchors . Likewise , since splitting failure is only considered relevant to uncracked concrete conditions , ψ cp , N is always shown equal to 1.0 in PROFIS Engineering when modeling cast-in-place or post-installed anchors for cracked concrete conditions .
but ψ cp , N determined from Eq . ( 17.4.2.7b ) shall not be taken less than 1.5h ef
/ c ac , where the critical distance c ac is defined in 17.7.6 .
For all other cases , including cast-in anchors , ψ cp , N shall be taken as 1.0 .
17.4 . 2.6 For anchors located in a region of a concrete member where analysis indicates no cracking at service load levels ……………..
17.7.6 Unless determined from tension tests in accordance with ACI 355.2 or ACI 355.4 , the critical edge distance c ac shall not be taken less than : Adhesive anchors ................................................ 2h ef Undercut anchors ................................................ 2.5h ef Torque-controlled expansion anchors ............................... 4h ef Displacement-controlled expansion anchors .......................... 4h ef
Example :
Example of critical edge distance requirements given in a mechanical anchor approval .
Splitting failure is influenced by the distance of an anchor from a fixed edge “ in a region of a concrete member where analysis indicates no cracking at service load levels ”. The parameter c ac that is used to calculate ψ cp , N is defined in ACI 318 as the “ critical edge distance required to develop the basic strength as controlled by concrete breakout or bond of a post-installed anchor in tension in uncracked concrete without supplementary reinforcement to control splitting .” ψ cp , N will be hown equal to 1.0 in PROFIS Engineering if the smallest fixed edge distance ( c a , min
) is greater than or equal to c ac
. Testing per the ICC-ES acceptance criteria AC193 and the ACI test standard ACI 355.2 is used to derive c ac values for mechanical anchors . Testing per the ICC-ES acceptance criteria AC308 and the ACI test standard ACI 355.4 is used to derive c ac values for adhesive anchor systems . c ac values derived from this testing are provided in an ICC-ESR . ACI 318-14 Section 17.7.6 provides c ac
-values for post-installed anchors ; however , these values are only intended to be used as “ guide values ” in the absence of c ac values derived from product-specific testing . PROFIS Engineering uses the c ac -value that is given in the ICC-ES evaluation report for an anchor to calculate ψ cp , N .
The value for ψ cp , N that PROFIS Engineering calculates will be limited to
ICC-ESR-1917 Table 3
DESIGN
Nominal anchor diameter ( in .) INFORMATION Symbol Units 3 / 8 1 / 2 5 / 8 3 / 4
Effective min . embedment
Min . member thickness
Critical edge distance
h ef in . 1-1 / 2 2 2-3 / 4 2 3-1 / 4 3-1 / 8 4 3-1 / 4 3-3 / 4 4-3 / 4
h min in . 3 1 / 4 4 5 5 4 6 6 8 5 6 8 5-1 / 2 6 8 8
c ac in . 6 4-3 / 8 4 4-1 / 8 5-1 / 2 4-1 / 2 7-1 / 2 6 6-1 / 2 8-3 / 4 6-3 / 4 12 10 8 9
MAXIMUM { c a , min / c ac
: 1.5h ef
/ c ac }
where c a , min is the smallest fixed edge distance less than c ac and h ef is the effective embedment depth that has been selected for the anchor being modeled .
Reference the Variables section of the PROFIS Engineering report for more information on the following parameters :
c a , min
: The smallest fixed edge distance being modeled .
c ac
: Value derived from testing per AC193 / ACI 355.2 or AC308 / ACI 355.4 for the anchor being modeled .
Example : Example of critical edge distance requirements given in an adhesive anchor approval .
ICC-ESR-Table 12
DESIGN INFORMATION
Critical edge distance — splitting ( for uncracked concrete )
Symbol Units
3 / 8 or # 3
1 / 2 or # 4
Nominal Rod Diameter ( in ).
5 / 8 or # 5
3 / 4 or # 6
7 / 8 or # 7
1 or # 8 c ac
- See Section 4.10.2 of this report .
# 9
1 / 4 or # 10 h ef
: Effective embedment depth that has been selected for the anchor being modeled .
Reference the Equations section of the PROFIS Engineering report for more information on the parameter ψ cp , N
.
71 NORTH AMERICAN PROFIS ENGINEERING ANCHORING TO CONCRETE DESIGN GUIDE — ACI 318-14 Provisions