PROFIS Design Guide: US-EN Summer 2021 | Page 357

COMBINED TENSION AND SHEAR LOAD

Parabolic
Results Utilization Status ( continued )
Results 318-14 Chapter 17 Provision Comments for PROFIS Engineering Status The following shear failure modes are considered for each type of anchor :
post-installed mechanical anchor steel strength : concrete breakout strength : concrete pryout strength :
post-installed adhesive anchor steel strength : concrete breakout strength : concrete pryout strength :
cast-in anchor steel strength : concrete breakout strength : concrete pryout strength : β V
= V ua ( i ) / ϕ steel
V sa β V
= V ua ( i ) / ϕ concrete
V cb or β V = V ua ( g )
/ ϕ concrete
V cbg β V
= V ua ( i ) / ϕ concrete
V cp or β V = V ua ( g )
/ ϕ concrete
V cpg β V
= V ua ( i ) / ϕ steel
V sa β V
= V ua ( i ) / ϕ concrete
V cb or β V = V ua ( g )
/ ϕ concrete
V cbg β V
= V ua ( i ) / ϕ concrete
V cp or β V = V ua ( g )
/ ϕ concrete
V cpg β V
= V ua ( i ) / ϕ steel
V sa β V
= V ua ( i ) / ϕ concrete
V cb or β V = V ua ( g )
/ ϕ concrete
V cbg β V
= V ua ( i ) / ϕ concrete
V cp or β V = V ua ( g )
/ ϕ concrete
V cpg where V ua ( i ) corresponds to the highest factored shear load acting on an individual anchor and V ua ( g ) corresponds to the total factored shear load acting on a group of anchors .
When the governing β N -value ( 51 %) and the governing β V
-value ( 130 %) for the example above are used in the parabolic equation ; the calculation results would be shown in PROFIS Engineering as follows :
β N , V
= ( β N ) 5 / 3 + ( β V
) 5 / 3
= ( 0.51 ) 5 / 3 + ( 1.3 ) 5 / 3 = 1.874
The parabolic equation has not been satisfied , so the report shows the “ Status ” as “ not recommended ”.
5 Combined tension and shear loads
β NV
= β N
E β N β V
E
Utilization β N [%]
0.510 1.300 5 / 3 188
+ β V
E
< = 1
Status
Not recommended
Part 5 of the PROFIS Engineering report shows the “ Status ” for parabolic equation calculation results as either “ OK ” if the equation is satisfied , or “ not recommended ” if it is not satisfied . PROFIS Engineering considers the parabolic equation to be satisfied if ( β N
) 5 / 3 + ( β V
) 5 / 3 is ≤ 1.0 . Reference the PROFIS Engineering design guide section on Utilization β N , V
[%] for additional information about PROFIS Engineering interaction calculations .
357 NORTH AMERICAN PROFIS ENGINEERING ANCHORING TO CONCRETE DESIGN GUIDE — ACI 318-14 Provisions