PART 4 SHEAR LOAD
Steel Failure Mode
Results ϕ steel
Results 318-14 Chapter 17 Provision Comments for PROFIS Engineering
ϕ steel
17.3.3 Strength reduction factor ϕ-for anchors in concrete shall be as follows when the load combinations of 5.3 are used :
( a ) Anchor governed by strength of a ductile steel element ( i ) Tension loads ........................................... 0.75 ( ii ) Shear loads ............................................ 0.65
( b ) Anchor governed by strength of a brittle steel element ( i ) Tension loads ........................................... 0.65 ( ii ) Shear loads ............................................ 0.60
PROFIS Engineering cast-in-place anchor portfolio .
• AWS D1.1 : 1 / 2 ” – 7 / 8 ” diameters
• Hex head , square head , heavy square head : 1 / 2 ” – 1 1 / 2 ” diameters
• Heavy hex head : 1 / 2 ” – 2 ” diameters
MATERIAL SPECIFICATION
AWS D1.1
ASTM F 1554
ASTM F 1554
ASTM F 1554
GRADE OR TYPE
DIAMETER ( d 0
) ( in )
TENSILE STRENGTH ( f uta
)
( ksi )
YIELD STRENGTH ( f ya
)
( ksi )
GROSS AREA ( in 2 )
EFFECTIVE AREA ( A se
)
( in 2 )
B |
0.500 |
65 |
51 |
0.196 |
|
B |
0.625 |
65 |
51 |
0.307 |
|
B |
0.750 |
65 |
51 |
0.442 |
|
B |
0.875 |
65 |
51 |
0.601 |
|
36 |
0.500 |
58 |
36 |
0.196 |
0.142 |
36 |
0.625 |
58 |
36 |
0.307 |
0.226 |
36 |
0.750 |
58 |
36 |
0.442 |
0.334 |
36 |
0.875 |
58 |
36 |
0.601 |
0.462 |
36 |
1.000 |
58 |
36 |
0.785 |
0.606 |
36 |
1.125 |
58 |
36 |
0.994 |
0.763 |
36 |
1.250 |
58 |
36 |
1.227 |
0.969 |
36 |
1.375 |
58 |
36 |
1.485 |
1.160 |
36 |
1.500 |
58 |
36 |
1.767 |
1.410 |
36 |
1.750 |
58 |
36 |
2.405 |
1.900 |
36 |
2.000 |
58 |
36 |
3.142 |
2.500 |
55 |
0.500 |
75 |
55 |
0.196 |
0.142 |
55 |
0.625 |
75 |
55 |
0.307 |
0.226 |
55 |
0.750 |
75 |
55 |
0.442 |
0.334 |
55 |
0.875 |
75 |
55 |
0.601 |
0.462 |
55 |
1.000 |
75 |
55 |
0.785 |
0.606 |
55 |
1.125 |
75 |
55 |
0.994 |
0.763 |
55 |
1.250 |
75 |
55 |
1.227 |
0.969 |
55 |
1.375 |
75 |
55 |
1.485 |
1.160 |
55 |
1.500 |
75 |
55 |
1.767 |
1.410 |
55 |
1.750 |
75 |
55 |
2.405 |
1.900 |
55 |
2.000 |
75 |
55 |
3.142 |
2.500 |
105 |
0.500 |
125 |
105 |
0.196 |
0.142 |
105 |
0.625 |
125 |
105 |
0.307 |
0.226 |
105 |
0.750 |
125 |
105 |
0.442 |
0.334 |
105 |
0.875 |
125 |
105 |
0.601 |
0.462 |
105 |
1.000 |
125 |
105 |
0.785 |
0.606 |
105 |
1.125 |
125 |
105 |
0.994 |
0.763 |
105 |
1.250 |
125 |
105 |
1.227 |
0.969 |
105 |
1.375 |
125 |
105 |
1.485 |
1.160 |
105 |
1.500 |
125 |
105 |
1.767 |
1.410 |
105 |
1.750 |
125 |
105 |
2.405 |
1.900 |
105 |
2.000 |
125 |
105 |
3.142 |
2.500 |
ACI 318-14 strength design provisions for steel failure in shear require calculation of a nominal steel strength ( V sa
). The nominal strength is multiplied by a strength reduction factor ( ϕ- factor ) to obtain a design strength ( ϕV sa
). ACI 318 anchoring-toconcrete provisions have traditionally defined ductile steel elements and brittle steel elements as follows :
• Ductile steel element — an element with a tensile test elongation of at least 14 percent and reduction in area of at least 30 percent
• Brittle steel element — an element with a tensile test elongation of less than 14 percent , or reduction in area of less than 30 percent , or both
PROFIS Engineering designates the ϕ-factor corresponding to steel failure “ ϕ steel
”.
When designing cast-in-place anchors , PROFIS Engineering uses the ϕ-factors given in ACI 318-14 Section 17.3.3 . The ϕ steel
-values for the cast-in-place anchors in the PROFIS Engineering portfolio correspond to the ϕ-factors given in Section 17.3.3 for ductile steel elements . In the absence of product-specific data , the ϕ-factors in Section 17.3.3 can be used as guide values for post-installed anchors ; however , ϕ-factors derived from product-specific testing should always be used for the actual design of post-installed anchors .
Post-installed mechanical anchors can be shown compliance under the International Building Code via testing per the ICC-ES acceptance criteria AC193 in conjunction with the ACI standard ACI 355.2 . Post-installed adhesive anchor systems can be shown compliance under the International Building Code via testing per the ICC-ES acceptance criteria AC308 in conjunction with the ACI standard ACI 355.4 . PROFIS Engineering uses the ϕ-factors derived from AC193 / ACI 355.2 or AC308 / ACI 355.4 testing , as given in the ICC-ESR for the anchor . The ϕ-factors in the ICC-ESR correspond to the ACI 318 ϕ-factors for “ ductile steel element ” and “ brittle steel element ”, as determined by the product testing and material properties for a specific anchor element .
Reference the Results section of the PROFIS Engineering report for more information on the following parameters :
V sa
: Nominal steel strength in tension
ϕV sa
: Design steel strength in tension
ϕ nonductile
: Seismic strength reduction factor
310 NORTH AMERICAN PROFIS ENGINEERING ANCHORING TO CONCRETE DESIGN GUIDE — ACI 318-14 Provisions