PART 4 SHEAR LOAD
 Pryout Failure Mode ( Pryout Bond )
 Results ϕ seismic
 Results 318-14 Chapter 17 Provision Comments for PROFIS Engineering
 ϕ seismic
 17.2.3.4.4 The anchor design tensile strength for resisting earthquake forces shall be determined from consideration of ( a ) through ( e ) for the failure modes given in Table 17.3.1.1 assuming the concrete is cracked unless it can be demonstrated that the concrete remains uncracked :
 ( a ) ϕ N sa for a single anchor or for the most highly stressed individual anchor in a group of anchors
 [ ϕN sa corresponds to steel failure ( tension ) in Table 17.3.1.1 ] ( b ) 0.75ϕN cb or 0.75ϕN cbg except that Ncb or Ncbg need not be calculated where anchor reinforcement satisfying 17.4.2.9 is provided
 [ ϕN cb or ϕN cbg correspond to concrete breakout failure ( tension ) in Table 17.3.1.1 ]
 ( c ) 0.75ϕN pn for a single anchor or for the most highly stressed individual anchor in a group of anchors [ ϕN pn corresponds to pullout failure ( tension ) in Table 17.3.1.1 ] ( d ) 0.75ϕN sb or 0.75ϕN sbg
 [ ϕN sb or ϕN sbg correspond to side-face blowout failure ( tension ) in Table 17.3.1.1 ]
 ( e ) 0.75ϕN a or 0.75ϕN ag
 [ ϕN a or ϕN ag correspond to bond failure ( tension ) in Table 17.3.1.1 ] where ϕ is in accordance with 17.3.3 .
 17.3.3 Strength reduction factor ϕ for anchors in concrete shall be as follows when the load combinations of 5.3 are used :
 ……………………………………………………………………………………………………
 ( c ) Anchor governed by concrete breakout , side-face blowout , pullout , or pryout strength Condition A
 Condition B ( i ) Shear loads 0.75 0.70
 Condition A applies where supplementary reinforcement is present except for pullout and pryout strengths .
 Condition B applies where supplementary reinforcement is not present , and for pullout and pryout strengths
 PROFIS Engineering calculations for concrete pryout failure in shear when seismic load conditions are being modeled :
 When designing an anchorage for seismic tension load conditions , ACI 318-14 provisions for non-steel failure modes in tension require calculation of a nominal strength ( N N
 ). The nominal strength is multiplied by two strength reduction factors ( ϕ-factors ): one ϕ-factor for the failure mode being considered , e . g . concrete breakout failure or bond failure ; and one ϕ-factor for seismic tension load conditions . The resulting design strength includes a seismic reduction factor of 0.75 : seismic design strength for non-steel failure modes = ( 0.75ϕN N
 ).
 PROFIS Engineering designates the 0.75 seismic tension reduction factor noted in ACI 318-14 Section 17.2.3.4.4 “ ϕ seismic
 ”. This reduction is only considered with respect to non-steel tension failure modes when calculating tension design strengths for both cast-in-place and post-installed anchors subjected to seismic tension loads .
 When designing an anchorage for seismic shear load conditions , ACI 318-14 strength design provisions for concrete pryout failure in shear require calculation of a nominal concrete pryout strength ( V cp or V cpg ) that is only multiplied by one ϕ-factor to obtain a shear design strength ( ϕV cp or ϕV cpg
 ). PROFIS Engineering designates this ϕ-factor “ ϕ concrete ”. The 0.75 seismic strength reduction factor
 ( ϕ seismic
 ) required per Section 17.2.3.4.4 is only relevant to tension calculations , and is therefore not applied to V cp or V cpg when the anchorage is being designed for seismic shear load conditions . The PROFIS Engineering report always shows
 ϕ seismic equal to 1.0 for shear concrete pryout calculations when seismic shear load conditions are being modeled .
 When calculating the design concrete pryout strength in shear for adhesive anchors , the parameter “ ϕ concrete
 ” in the PROFIS Engineering report corresponds to the “ Condition B ” ϕ-factor for shear given in the ICC-ESR for the anchor .
 Per ACI 318-14 Section 17.3.3 , Condition A is not considered for pryout strength calculations .
 Reference the Results section of the PROFIS Engineering report for more information on the following parameters :
 V cp or V cpg : Nominal concrete pryout strength in shear ϕV cp or ϕV cpg
 : Design concrete pryout strength in shear
 ϕc oncrete
 : Strength reduction factor for shear concrete pryout failure single anchor : design concrete pryout strength = ϕ concrete
 V cp anchor group : design concrete pryout strength = ϕ concrete
 V cpg
 248 NORTH AMERICAN PROFIS ENGINEERING ANCHORING TO CONCRETE DESIGN GUIDE — ACI 318-14 Provisions