Product Technical Guides : US-EN Modular Systems Product Technical Guide | Page 99

Modular Support Systems Technical Guide , Edition 1
3.0 MODULAR SUPPORT SYSTEM 3.2.4 MT SPLICE CONNECTORS MT-ES-60
Description
Extension splice for channel .
Material Specifications
Standard 1 Grade 1 F y , ksi ( MPa ) F u
, ksi ( MPa ) GB / T 700 Q235 B 34.08 ( 235 ) 53.66 ( 370 )
1 . Mechanical properties of GB / T 700 Grade Q235 B meet or exceed the mechanical properties of ASTM A1011 SS Grade 33 .
Corrosion Protection
Electro-Galvanized ( EG )
MT-ES-60
Hot-Dipped Galvanized ( HDG )
MT-ES-60 OC
Ordering Information
Description
Weight Per Piece lbs ( kg )
Quantity Piece ( s )
Item No .
MT-ES-60 5.45 ( 2.47 ) 8 2332415 MT-ES-60 OC 5.45 ( 2.47 ) 8 2332416
��
����
�������
����
���������
���
�������
��
������
���
���������
mm ( in )
Figure 63 - Splice Extension for MT Channel
Table 183 - Allowable Strength Design ( ASD ) Load Data 1 , 2 , 3
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
2,320
200
1,655
( 10.33 )
( 0.90 )
( 7.37 )
1 . Minimum safety factor , Ω , for tabulated values is 2.6 . 2 . Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD ) values . 3 . See Figure 63 .
Table 184 - Limit State Design ( LSD ) Load Data 1 , 2
A . MT-60
* Splice connector is attached to MT Channels using 4 x MT-CTAB screws .
Figure 64 - Splice Extension for MT Channel
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
3,230
265
2,300
( 14.37 )
( 1.19 )
( 10.24 )
1 . Maximum resistance factor , ϕ , for tabulated values is 0.55 . 2 . See Figure 63 .
Table 185 - Allowable Strength Design ( ASD ) Load Data 1 , 2 , 3
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
835
80
1,320
( 3.72 )
( 0.37 )
( 5.88 )
1 . Minimum safety factor , Ω , for tabulated values is 2.65 . 2 . Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD ) values . 3 . See Figure 64 .
Table 186 - Limit State Design ( LSD ) Load Data 1 , 2
A . MT-60
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
1,055
95
1,705
( 4.70 )
( 0.44 )
( 7.59 )
1 . Maximum resistance factor , ϕ , for tabulated values is 0.5 . 2 . See Figure 64 .
2023
97