Product Technical Guides : US-EN Modular Systems Product Technical Guide | Page 88

Modular Support Systems Technical Guide , Edition 1
3.0 MODULAR SUPPORT SYSTEM 3.2.3 MT SYSTEM CONNECTORS MT-C-GL A OC
Description
Adjustable connector for MT-80 ( long side ), MT-90 , and MT-100 girders .
Material Specifications
Standard 1 Grade 1 F y , ksi ( MPa ) F u
, ksi ( MPa ) GB / T 1591 Q355 B 51.49 ( 355 ) 68.17 ( 470 )
1 . Mechanical properties of GB / T 1591 Grade Q355 B meet or exceed the mechanical properties of ASTM A1011 SS Grade 50 .
Corrosion Protection
Hot-Dipped Galvanized ( HDG )
����� “) �
��
����� “)
MT-C-GL A OC
Ordering Information
�����
����� “ x ������ “)
���
������ “)
Description
Weight Per Piece lbs ( kg )
Quantity Piece ( s )
Item No .
MT-C-GL A OC 2.53 ( 1.15 ) 10 2272069
�� “) ���
mm ( in )
���
������ “)
Figure 45 - MT Single Angle Connection
Table 147 - Allowable Strength Design ( ASD ) Load Data 1 , 2 , 3
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
2,995
2,620
3,000
( 13.33 )
( 11.66 )
( 13.36 )
1 . Minimum safety factor , Ω , for tabulated values is 2.1 . 2 . Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD ) values . 3 . See Figure 45 .
Table 148 - Limit State Design ( LSD ) Load Data 1 , 2
A . MT-80 ( long side )/ 90 / 100 ( short side )
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
4,495
3,935
4,510
( 20.00 )
( 17.52 )
( 20.08 )
1 . Maximum resistance factor , Φ , for tabulated values is 0.7 . 2 . See Figure 45 .
Figure 46 - MT Double Angle Connection
Table 149 - Allowable Strength Design ( ASD ) Load Data 1 , 2 , 3
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
M y ft lb ( kN m )
6,560
5,275
5,615
1,320
( 29.20 )
( 23.47 )
( 24.99 )
( 1.79 )
1 . Minimum safety factor , Ω , for tabulated values is 2.2 . 2 . Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD ) values . 3 . See Figure 46 .
Table 150 - Limit State Design ( LSD ) Load Data 1 , 2
A . MT-80 ( long side )/ 90 / 100 ( short side )
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
M y ft lb ( kN m )
8,530
7,635
7,970
1,870
( 37.96 )
( 33.97 )
( 35.47 )
( 2.54 )
1 . Maximum resistance factor , ϕ , for tabulated values is 0.65 . 2 . See Figure 46 .
2023
86