Modular Support Systems Technical Guide , Edition 1
3.0 MODULAR SUPPORT SYSTEM 3.2.3 MT SYSTEM CONNECTORS MT-C-GL OC
Description
Angle connector for MT-80 ( long side ), MT-90 , and MT-100 girders . Use as base for attachment to concrete or steel ( X-BT / S-BT / F-BT compatible ).
Material Specifications
Standard 1 Grade 1 F y , ksi ( MPa ) F u
, ksi ( MPa ) GB / T 1591 Q355 B 51.49 ( 355 ) 68.17 ( 470 )
1 . Mechanical properties of GB / T 1591 Grade Q355 B meet or exceed the mechanical properties of ASTM A1011 SS Grade 50 .
����� “) �
Corrosion Protection
Hot-Dipped Galvanized ( HDG )
�����
����� “)
MT-C-GL OC
Ordering Information
Description
Weight Per Piece lbs ( kg )
Quantity Piece ( s )
Item No .
MT-C-GL OC 2.64 ( 1.2 ) 10 2272066
����� “)
���
�� “) ���
mm ( in )
���
������ “)
���
������ “)
Figure 41 - MT Single Angle Connection
Table 139 - Allowable Strength Design ( ASD ) Load Data 1 , 2 , 3
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
3,070
2,610
3,240
( 13.65 )
( 11.6 )
( 14.45 )
1 . Minimum safety factor , Ω , for tabulated values is 2.2 . 2 . Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD ) values . 3 . See Figure 41 .
Table 140 - Limit State Design ( LSD ) Load Data 1 , 2
A . MT-80 ( long side )/ 90 / 100
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
4,910
3,680
4,610
( 21.83 )
( 16.38 )
( 20.52 )
1 . Maximum resistance factor , Φ , for tabulated values is 0.65 . 2 . See Figure 41 .
Figure 42 - MT Double Angle Connection
Table 141 - Allowable Strength Design ( ASD ) Load Data 1 , 2 , 3
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
M y ft lb ( kN m )
M z ft lb ( kN m )
7,340
5,230
5,620
1,320
875
( 32.65 )
( 23.27 )
( 25.00 )
( 1.79 )
( 1.19 )
1 . Minimum safety factor , Ω , for tabulated values is 2.2 . 2 . Multiply tabulated values by 1.5 to obtain minimum Load and Resistance Factor Design
( LRFD ) values . 3 . See Figure 42 .
A . MT-80 ( long side )/ 90 / 100
Table 142 - Limit State Design ( LSD ) Load Data 1 , 2
F x lb ( kN )
F y lb ( kN )
F z lb ( kN )
M y ft lb ( kN m )
M z ft lb ( kN m )
10,690
7,360
7,975
1,870
1,140
( 47.58 )
( 32.76 )
( 35.49 )
( 2.54 )
( 1.55 )
1 . Maximum resistance factor , Φ , for tabulated values is 0.65 . 2 . See Figure 42 .