Product Technical Guides : US-EN Firestop Systems Guide For Specifiers | Page 83

Firestop Selection Chart JOINT Fire rating (F rating) Type of joint — description Max. joint width (inches) Movement capability Hilti product used System number Sealant depth (inches) See page > Floor to floor, wall to floor and wall to wall joints 14% CFS-SP WB FF-D-1013 1/8" 544 C Concrete floor to floor joint 2 hr 6" 10% CFS-S SIL SL FF-D-1039 1/2" 547 C Concrete floor to floor joint 4 hr 3" 12.50% CFS-S SIL SL FF-D-1125 1/2" 546 C Concrete floor to floor joint 2 hr 3" 33.00% CFS-S SIL SL, CFS-S SIL GG FF-D-1126 1/4" 547 C Concrete floor to wall joint 2 hr 3-1/2" 14% CFS-SP WB FW-D-1013 1/8" 548 C Concrete floor to wall joint 2 hr 6" 10% CFS-S SIL SL FW-D-1037 1/2" 549 C Concrete floor to wall joint 2 hr 3" 17% CP 606 FW-D-1071 1/4" 550 C Concrete floor to wall joint 2 hr 3" 33% CFS-S SIL SL, CFS-S SIL GG FW-D-1093 1/4" 551 C Concrete or block wall perpendicular and parallel to concrete over metal deck (includes roof deck) (top of wall) 2 hr 3/4" 33% CP 606 HW-D-0081 1/2" 552 C Concrete or block wall to concrete over fluted metal deck (top-of-wall) 1 or 2 hr 1" 12.50% CFS-SP WB HW-D-0098 1/8" 553 C Concrete or block wall to concrete over metal deck with optional use of spray-on fireproofing (parallel) (top-of-wall) 2 hr 1" 12.50% CFS-SP WB HW-D-0181 1/8" 555 C Concrete or block wall parallel to concrete over metal deck with spray-on fireproofing (I beam/bar joist through joint) (top of wall) 2 hr 1" 25% CFS-SP WB HW-D-0258 1/8" 556 C Concrete or block wall to concrete floor or hollow core floor (Sealant only) (top of wall) 2 hr 1" 12.50% CP 606 HW-D-0268 1/2" 558 C Concrete or block wall perpendiular to concrete over metal deck (includes roof deck) (top of wall — one side access) 2 hr 2" 12.50% CFS-SP WB HW-D-0285 1/8" 559 C Concrete or block wall parallel to concrete over metal deck (includes roof deck) (top of wall - one side access) 2 hr 2" 12.50% CFS-SP WB HW-D-0286 1/8" 556 C Top of concrete or block wall to fluted steel roof deck 2 hr 1" 12.50% CFS-SP WB HW-D-0389 1/8" 561 C Concrete or block wall to bottom of fire-proofed steel I-beam to concrete over metal deck 2 hr 2" 12.50% CFS-SP WB HW-D-0440 1/8" 563 C Concrete or block wall perpendicular to concrete over metal deck with optional use of spray-on fireproofing (top of wall) 2 hr 3-1/2" 14% CFS-SP WB HW-D-1037 1/8" 564 C Concrete or block wall to concrete floor 3 hr 3-1/4" 25% CFS-SP WB HW-D-1058 1/8" 565 C Block wall to underside of flat concrete 2 hr 3" 17% CP 606 HW-D-1078 1/4" 566 C Concrete or block wall to wall joint (sealant only) 2 hr 1" 12.50% CP 606 WW-D-0032 1/2" 567 C Concrete or block wall perpendicular to gypsum wall (wall to wall) (Sealant only) 1 or 2 hr 3/4" 17% CP 606, CFS-S SIL GG WW-D-0040 5/8" 568 C Concrete wall to wall joint 2 hr 3" 17% CP 606 WW-D-1080 1/4" 569 C Concrete wall to wall joint 2 hr 3-1/2” 14% CFS-SP WB WW-D-1084 1/8” 570 C Concrete wall to wall joint 2 hr 3" 33% CFS-S SIL GG WW-D-1129 1/4" 571 C Concrete wall to gypsum wall (gyp sitting on top of concrete) 1 or 2 hr 3/4" - CP 606, CP 601S, CFS-S SIL GG WW-S-0048 5/8" 572 3-1/2" 2 hr Concrete floor to floor joint C Base material * Refer to UL System. C Concrete or concrete block G Gypsum W Wood Hilti Firestop Saving lives through innovation and education 81