Product Technical Guides : US-EN Firestop Systems Guide For Specifiers | Page 687

Estimating Tables Estimating tables for through-penetrations TABLE 1 TABLE 2 Nominal pipe size Pipe O.D. 1/2" General estimation table for CP 648-E (Length of Wrap Strip required for different pipe diameters) Area (sq. in.) 0.55 1.3 1.33 1-1/2" 1.9 2.83 2" 2.4 4.52 3" 3.5 9.62 4" 4.5 15.9 6" 6.6 34.19 8" 8.6 58.06 10" 10.8 91.56 12" 12.75 127.61 Pipe O.D. based on schedule 40 steel pipe and plastic pipe Nominal Pipe Size Length of CP 648-E Wrap Strips (3/16" thick) Required* (Number of layers of Wrap Strips) 1-1/2" 1 2 3 4 8" 16" 26" 37" 2" 9" 20" 31" 43" 3" 12" 27" 41" 58" 4" - 30" 50" 70" 6" - - 71" 97" 8" - - - 122" 10" - - - 142" 12" - - - 167" 0.84 1" Calculation chart for pipe areas Estimations based upon Schedule 40 PVC Plastic Pipe. * E stimated quantities are approximate. No allowance has been made for waste. TABLE 3 Estimation chart: volume of firestop at 1/2" depth (in 3 ), per penetration. Estimated volume of material required to fill the annular space between the O.D. of a penetrating pipe and the I.D. of the opening through which it passes. 0.84 1 0.12 1-1/2 2 1.05 1.3 1.9 2.4 3.5 4.5 5.6 6.6 8.6 10.8 12.8 5 6 8 10 12 Nominal pipe size (I.D.) 1/2 3/4 1 1-1/2 2 3 4 0.60 0.46 0.22 1.30 1.14 0.90 0.16 2-1/2 2.18 2.02 1.78 1.04 3 3.26 3.10 2.86 2.12 1.28 3-1/2 4.54 4.38 4.14 3.40 2.54 4 6.00 5.84 5.62 4.86 4.02 1.48 5 9.54 9.38 9.14 8.40 7.56 5.00 6 13.86 13.70 13.46 12.72 11.86 9.32 6.18 1.82 7 18.96 18.80 18.56 17.82 16.98 14.42 11.28 6.92 2.14 8 24.84 24.68 24.46 23.70 22.86 20.32 17.18 12.82 8.02 Actual pipe diameter (in.) (O.D.*) Opening diameter 0.20 1.86 9 31.52 31.36 31.12 30.38 29.54 26.98 23.84 19.48 14.70 2.76 10 38.98 38.82 38.58 37.84 36.98 34.44 31.30 26.94 22.16 10.22 12 56.24 56.08 55.86 55.10 54.26 51.72 48.58 44.22 39.42 27.50 14 76.66 76.50 76.26 75.52 74.66 72.12 68.98 64.62 59.84 47.90 31.14 13.12 16 100.20 100.10 99.82 99.06 98.22 95.68 92.54 88.18 83.38 71.46 54.70 36.68 10.74 Coverages are based on the outside diameter of schedule 40 steel pipe. * For insulated pipes, use the outside diameter of the insulation. • For 1/4" depth, divide above number by 2. • For 1" depth, multiply above number by 2. • For 5/8" depth, multiply above number by 1.25. • For 1-1/4" depth, multiply above number by 2.5. • For 3/4" depth, multiply above number by 1.50. Note: Walls require firestop on both sides; multiply above number again by 2. Estimate only. Assumes no waste. TABLE 4 Estimation chart: volume of firestop used in retaining collar around vented plastic pipe* Pipe O.D. (in.) FS-ONE MAX volume required (cu. in.) Collar I.D. (in.) Approximate # of 10.1 Oz.Tubes required to fill one collar Collar length required** (in.) 4 4.5 6.5 30.22 1.66 21.42 3 3.5 5.5 24.73 1.35 18.28 2 2.4 4.4 18.68 1.03 14.82 1.5 1.9 3.9 15.94 0.88 13.25 1 1.4 3.4 13.19 0.72 11.68 * Applies to Hilti listed systems using retaining colllars — refer to system(s) for details. Volumes are approximate, and assumes no waste. ** Collar length assumes the ends overlap 1". Volume of FS-ONE calculated with retaining collar item no. 283225s Pipe I.D. (in.) Hilti Firestop Saving lives through innovation and education 685