Product Technical Guides : US-EN Firestop Systems Guide For Specifiers | Page 36

FLEXIBLE FIRESTOP SEALANT CP 606 Product description • An acrylic based firestop sealant that provides movement capability in fire rated joints and seals through-penetration applications Product features • • • • • • • • Silicone free Halogen, asbestos and solvent free Paintable Tested up to 33% movement with 500 cycles in accordance to UL 2079 and ASTM 1966 Smoke and fume resistant Easy clean up with water Single component systems available Meets LEED™ requirements for indoor environmental quality credit 4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paints and Coatings Areas of application • • • • • • • • Sealing construction/expansion joints Top-of-wall joints Metal pipes Cable bundles HVAC penetrations For use with Various base materials such as masonry, concrete, gypsum, etc. Wall and floor assemblies rated up to 3 hours Examples • Where a gypsum wall assembly meets the underside of a metal or concrete deck • Sealing expansion joints to impede the passage of fire, smoke and toxic fumes • Sealing around HVAC penetrations through fire-rated assemblies Installation instructions • See Hilti Literature or third-party listings for complete application and installation details FILL, VOID OR CAVITY MATERIAL FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS AND JOINT SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY 66Y7 FM $33529(' Technical Data* Chemical basis Acrylic based firestop sealant Color Available in red, white and gray Application temperature )RU3HQHWUDWLRQ)LUH6WRSV Skin-forming &RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH Hilti Firestop Saving lives through innovation and education 34 time 40°F to 104°F (5°C to 40°C) Approx. 15 min Curing time Approx. 3 mm / 3 days Average volume shrinkage (ASTM C1241) 22% Movement capability Approx. 10% Temperature resistance –22°F to 176°F (–30°C to 80°C) Surface burning characteristics (ASTM E 84-96) Flame Spread: 10 Smoke Development: 0 Sound transmission classification (ASTM E 90-99) 56 (Relates to specific construction) Tested in accordance with UL 2079, ASTM E 814, ASTM E 1966, ASTM E 84, UL 1479 , ASTM G21 *At 73°F (23°C) and 50% relative humidity FILL, VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS LABORATORIES, INC. FOR USE IN TROUGH-PENETRATION