Product Technical Guides : US-EN Firestop Systems Guide For Specifiers | Page 36
FLEXIBLE FIRESTOP SEALANT CP 606
Product description
• An acrylic based firestop sealant that provides movement capability in fire rated
joints and seals through-penetration applications
Product features
•
•
•
•
•
•
•
•
Silicone free
Halogen, asbestos and solvent free
Paintable
Tested up to 33% movement with 500 cycles in accordance to UL 2079 and
ASTM 1966
Smoke and fume resistant
Easy clean up with water
Single component systems available
Meets LEED™ requirements for indoor environmental quality credit 4.1 Low
Emitting Materials, Sealants and Adhesives and 4.2 Paints and Coatings
Areas of application
•
•
•
•
•
•
•
•
Sealing construction/expansion joints
Top-of-wall joints
Metal pipes
Cable bundles
HVAC penetrations
For use with
Various base materials such as masonry, concrete, gypsum, etc.
Wall and floor assemblies rated up to 3 hours
Examples
• Where a gypsum wall assembly meets the underside of a metal or concrete
deck
• Sealing expansion joints to impede the passage of fire, smoke and toxic fumes
• Sealing around HVAC penetrations through fire-rated assemblies
Installation instructions
• See Hilti Literature or third-party listings for complete application and
installation details
FILL, VOID OR CAVITY MATERIAL
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS AND
JOINT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
FM
$33529('
Technical Data*
Chemical basis Acrylic based firestop sealant
Color Available in red, white and gray
Application temperature
)RU3HQHWUDWLRQ)LUH6WRSV
Skin-forming
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
Hilti Firestop
Saving lives
through innovation
and education
34
time
40°F to 104°F (5°C to 40°C)
Approx. 15 min
Curing time Approx. 3 mm / 3 days
Average volume shrinkage (ASTM C1241) 22%
Movement capability Approx. 10%
Temperature resistance –22°F to 176°F (–30°C to 80°C)
Surface burning characteristics
(ASTM E 84-96) Flame Spread: 10
Smoke Development: 0
Sound transmission classification
(ASTM E 90-99) 56
(Relates to specific construction)
Tested in accordance with UL 2079, ASTM E 814, ASTM E 1966,
ASTM E 84, UL 1479 , ASTM G21
*At 73°F (23°C) and 50% relative humidity
FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION