FLOOR DEVICE STANDOFF COMPONENT
(FOR USE WITH CP 680 P/M)
Product description
• Standoff component provides a pre- or post-poured solution for water
containment and riser clamp support of vertical pipe penetrations
• Fully threaded coupler for use with height extensions and assembly of standoff
component to CP 680 P/M
Product features
Installed CP 680 with coupler and CFS-DID lid.
• Standoff component may be installed before or after the concrete is poured
• Post poured installation allows floor finisher to work without obstacles or risk of
damaging pre-installed standoffs
• Designed to meet requirements for a minimum 2" standoff above substrate surface
• The completed application can provide an effective solution for fire protection,
water containment and riser clamp support for vertical pipe penetrations*
• Tested load values according to UL 203
Areas of application
• Vertical pipe penetrations, metallic and non-metallic
• Support of vertical pipe clamps for CP 680 P/M
• Areas subject to flood or needing water containment
* Riser clamp support for CP 680 P/M only. Standoff component may be used with Hilti Firestop Drop in device CFS-DID
for standoff requirements and water containment. Standoff component is not intended for use with CFS-DID as a load
bearing element.
It is recommended that the standoff component be installed before tightening the PT deck.
Installed CP 680 with standoff component and
CP 680 lid.
Installed CP 680 with standoff component
Technical Data
Dimensions (height) 2 inch diameter: 3.15”
3 inch diameter: 3.15”
4 inch diameter: 3.4”
6 inch diameter: 3.4”
Installed height
(height above coupler after threading) 2 inch diameter: 2.35”
3 inch diameter: 2.16”
4 inch diameter: 2.32”
6 inch diameter: 2.16”
Minimum Slab Thickness 2 inch diameter: 4.5” slab
3 inch diameter: 5” slab
4 inch diameter: 5.5” slab
6 inch diameter: 5.6” slab
Consistency Coupler: Polypropylene
Standoff: Metal with plastic overlay
Color Red
Storage temperature 40 °F (5 °C) to 104 °F (40 °C)
Curing time Non-curing
Tested in accordance with ASTM G21
Load Values (maximum allowable)* per UL 203
Standoff diameter
Hilti Firestop
Saving lives
through innovation
and education
28
Metallic and non-metallic pipes
*Check local codes and requirements.
lb
2 inch 750
3 inch 1050
4 inch 1500
6 inch 2650