Product Technical Guides : US-EN Firestop Systems Guide For Specifiers | Page 26
CAST-IN FIRESTOP DEVICES
CP 680-P / CP 680-M
For use in
• Dust and fiber free environments such as hospitals, computer centers and
laboratories
• Concrete floor assemblies rated up to 4 hours
Product description
CP 680-P in concrete over
wood forms
CP 680-M in concrete over
wood forms
•
•
•
•
•
A one-step cast-in firestop sleeve for a variety of penetrating items
Helps reduce labor costs and increase productivity
Ready-to-use out of the package
Internationally tested and approved by UL and FM
Reduces the chance of project delays due to failed inspections
Product features
•
•
•
•
•
•
No expiration date alleviates shelf life concerns
Quick and simple installation
Easy to align and install a faster layout
Easy and simple vertical connections
Integrated moisture and smoke seal
Innovative adapter for metal deck applications
Installation and applications
CP 680-P over metal deck
CP 680-M over metal deck
• Concrete floors (flat concrete or concrete over metal deck) from 2.5" (63 mm)
thickness
CP 680-M:
- Metallic penetration (Insulated and non-insulated)
- EMT and electrical conduits
- Cable bundles
- Multiple pipes
CP 680-P:
Addresses all applications for CP 680-M as well as the following:
- Combustible pipes such as PVC, CPVC, ABS, ENT and FRPP
- Fresh and waste water pipes
Installation instructions
• See Hilti Literature or third-party listings for complete application and
installation details
FIRESTOP DEVICE
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
5N76
FM
$33529('
Visit fbcsystemcompatible.com.
)RU3HQHWUDWLRQ)LUH6WRSV
FBC™ is a trademark of
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
the Lubrizol Corporation.
Hilti Firestop
Saving lives
through innovation
and education
24
FILL, VOID OR CAVITY MATERIALS
Technical Data
ID Footprint Opening required thru metal deck
2" 3-3/4" x 4-1/2" 3-1/2" diameter
3" 4-3/4" x 5-5/8" 4-1/2" diameter
4" 6-3/8" x 6-3/4" 5-1/2" diameter
6" 9" x 9-1/2" 7-1/4" diameter
Expansion temperature 392°F (200°C)
Expansion rate 1:50 (unrestrained)
1:30 (Load expansion, Load = 20g/cm 3 )
Standard height 8"
Temperature resistance Maximum 212°F (100°C)
Color CP 680-P: red
Mold and Mildew (ASTM G-21) Mold and mildew resistant
Tested in accordance with UL 1479, ASTM E 814, ASTM G21,
CAN/ULC-S115, UL 2043
Internationally tested and approved
CP 680-M: black