Product Technical Guides : US-EN Firestop Systems Guide For Specifiers | Page 22
FIRESTOP CABLE COLLAR CFS-CC 4"
Product description
• Firestop Cable Collar is an easy to use cable management firestop solution
covering max 4" openings in floors and walls
• Surface mounted, sealant free solution for new and pre-existing cable applications
• Economical and user-friendly solution for max 4" openings that are up to 100%
visually filled with cables
• Does not require surface preparation in order to firestop. No cutting the floor or
wall in order to retrofit a solution around pre-existing cables
Product features
• No expiration date alleviates shelf life concerns
• Fast and easy firestop solution for a maximum 4" opening (sleeved or un-sleeved)
• Simple and intuitive firestop solution for openings that are 100% visually filled
(max 4" diameter openings)
• Surface mounted, sealant free solution
• Solves problematic cable applications
• Re-penetrable for future cable capacity
• Pre-cured, pre-formed firestop material does not expire, eliminating shelf-life concerns
• Fast and easy topside solution for floors. No mineral wool, no sealant required.
• Immediately functional after installation
• Meets LEED™ requirements for indoor environmental quality credit 4.1 Low
Emitting Materials
• Low VOC content and no CFCs or HCFCs
Areas of application
• Single and bundled cables in floors and walls
• New and existing cable applications
• Membrane penetrations
Installation instructions
• See Hilti Literature or third-party listings for complete application and
installation details
FIRESTOP DEVICE
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL DIRECTORY OF PRODUCTS CERTIFIED
FOR CANADA AND UL FIRE RESISTANCE
DIRECTORY 5N76
Hilti Firestop
Saving lives
through innovation
and education
20
Technical Data
OD (device only) 6"
Height 3"
Color Red
Density Approx. 0.27 g/cm 3
Application temperature 40° F to 104° F (5° C to 40° C)
Temperature resistance 5° F to 140° F (-15° C to 60° C)
Intumescent activation Approx. 392° F (200° C)
Expansion ratio (unrestricted) Approx. 1:3
Surface burning characteristics
(ASTM E 84-10b) Flame Spread: 10
Smoke Development: 15
Sound Transmission Classification
(ASTM E 90-07) STC 59 (blank)
STC 56 (cable bundle)
Tested in accordance with ASTM E 814, ASTM E 90, CAN/ULC-S115,
UL 1479, ASTM E 84 (based upon CFS-PL)