Product Technical Guides : US-EN Direct Fastening - Volume 1 Edition 22 | Page 115

Direct Fastening Technical Guide , Edition 24
Load reduction with wire hanger angle 1 , 2 , 3
Angle from vertical 0 ° 15 ° 30 ° 45 ° 60 ° Load adjustment factor 1.00 0.96 0.86 0.70 0.50
1 . The tabulated load adjustment values are for loads in the vertical down orientation as depicted in the accompanying figure . 2 . Fastener and clip installation shall be such that the angle of the wire extends away from the nail . 3 . Load adjustment factor shall be multiplied by the applicable X-MW allowable load .
Spiral HVAC single wall with 10 ' hanging space 1
Weight ( lbs )
Diameter
Circumference
26 Gauge
24 Gauge
22 Gauge
8 "
2 ' 2 "
23
29
36
12 "
3 ' 2 "
35
44
54
16 "
4 ' 2 "
47
59
72
20 "
5 ' 3 "
58
73
90
24 "
6 ' 3 "
70
88
108
28 "
7 ' 4 "
81
103
126
32 "
8 ' 5 "
93
117
144
36 "
9 ' 5 "
105
132
162
Spiral HVAC double wall with 10 ' hanging space 1
Inside Diameter
Outside Gauge
Inside Gauge
Weight per ft . ( lb / ft )
8 "
26
26
6
12 "
26
26
8
Weight of rectangular duct , based on 8 ' and 10 ' hanging space 1
Rectangle Duct Size ( height + width )
Weight per ft . 20 Gauge 22 Gauge
Weight / 8 ft . Weight / 10 ft . 8 x 6 " - 3.57 28.56 35.70 10 x 6 " - 4.08 32.64 40.80 12 x 6 " - 4.59 36.72 45.90 14 x 10 " - 6.12 48.96 61.20 16 x 16 " - 8.16 65.28 81.60 24 x 12 " - 9.18 73.44 91.80 36 x 18 " - 13.77 110.16 137.70 40 x 22 " 18.34 - 146.73 183.42 50 x 20 " 20.71 - 165.67 207.08
1 . Weight per foot is calculated based on SMACNA HVAC Systems Duct Design .
115