Product Technical Guides : US-EN Direct Fastening - Volume 1 Edition 22 | Page 76

3.2.14.4 INSTALLATION INSTRUCTIONS
Installation Instructions For Use ( IFU ) are included with each product package . They can also be viewed or downloaded online at www . hilti . com . Because of the possibility of changes , always verify that downloaded IFU are current when used .
Proper installation is critical to achieve full performance . Training is available on request . Contact Hilti Technical Services for applications and conditions not addressed in the IFU .
Stainless steel T-bar for fastening cables to steel structures 1 , 2 , 3
Slotted T-bar 1 . Attach Slotted T-bar on installed X-BT fastener . Do not exceed Maximum Tightening Torque ,
T max
= 6 ft-lb ( 8 Nm ).
2 . Place and attach cable to Slotted T-bar .
Crimp T-bar
1 . Attach Crimp T-bar on installed X-BT fastener . Do not exceed Maximum Tightening Torque ,
T max
= 6 ft-lb ( 8 Nm ).
2 . Insert cable into Crimp T-bar and wrap Crimp T-bar around cable .
1 These are abbreviated instructions which may vary by application . ALWAYS review / follow the instructions accompanying the product . 2 Reference Section 3.2.14.5 for information on number and size of cables . 3 Space T-bars at approximately 24 " to 32 " ( 60-80 cm ). Adjust as necessary to control cable sagging .
76