Product Technical Guides : US-EN Anchor Fastening - August 2021 | Page 436

Table 8 — Design information , Hilti HDI-P TZ , in accordance with CSA A23.3 1
Setting information Symbol Unit
Nominal anchor size / internal thread dia . ( in )
Ref
3 / 8 CSA A23.3
Anchor O . D . d a in . ( mm )
Effective embedment h ef in . ( mm )
0.561 ( 14.25 )
Steel embed . material resistance factor for reinforcement φ s - 0.85 8.4.3
Resistance modification factor for tension , steel failure modes 2 , 3 R s , N - 0.70 D . 5.3 b )
Min . specified yield strength f ya psi ( N / mm 2 )
Min . specified ultimate strength f uta psi ( N / mm 2 )
Effective-cross sectional steel area in tension A se , N in 2
( mm 2 )
Factored steel resistance in tension 4 N sa lb ( kN )
Concrete material resistance factor φ c - 0.65 8.4.2
3 / 4 ( 19 )
70,400 ( 484 )
88,000 ( 605 )
0.071 ( 45.8 )
6,250 ( 27.8 )
D . 6.1.2 Eq . D . 2
Anchor category - - 1 D . 5.3 c ) Resistance modification factor for tension , concrete failure 3 R c , N - 0.60
Coeff . for factored conc . breakout resistance , uncracked concrete
Coeff . for factored conc . breakout resistance , cracked concrete k c , uncr
k c , cr in-lb ( SI )
in-lb ( SI )
24 ( 10.0 )
17 ( 7.1 )
D . 6.2.2
D . 6.2.2
Modification factor for anchor resistance , tension , uncracked conc . 5 ψ c , N - 1.0 D . 6.2.6
Critical edge distance c ac in . ( mm )
Factored pullout resistance in 20 MPa uncracked concrete 6 N pr , uncr lb ( kN )
Factored pullout resistance in 20 MPa cracked concrete 6 N pr , cr lb ( kN )
Factored pullout resistance in 20 MPa cracked concrete , seismic 6 N pr , eq lb ( kN )
6 ( 152 )
N / A D . 6.3.2
495 ( 2.2 )
490 ( 2.2 )
D . 6.3.2
D . 6.3.2
Resistance modification factor for shear , steel failure modes 2 , 3 R s , V - 0.65 D . 5.3 b )
Factored steel resistance in shear 7 V sa lb ( kN )
Factored steel resistance in shear , seismic 7 V sa , eq lb ( kN )
975 ( 4.3 )
975 ( 4.3 )
Resistance modification factor for shear , concrete failure modes 3 R c , V - 0.70
Coefficient for pryout resistance k cp - 1.0 D . 7.3
1 Design information is taken from ICC-ES ESR-4236 , dated July 2018 , table 2 , and converted for use with CSA A23.3 Annex D . 2 The HDI-P TZ is considered a brittle steel element as defined by CSA A23.3 Annex D Section D . 2 . 3 All values of R are applicable with the load combinations of CSA A23.3 Chapter 8 . For concrete failure modes , no increase for Condition A is permitted . 4 N sar = N sa φ s R s , N where N sa tabular value above is precalculated from A se , N f uta . 5 For all design cases , ψ c , N = 1.0 . The appropriate effectiveness factor for cracked concrete ( k c , cr ) or uncracked concrete ( k c , uncr ) must be used . 6 For all design cases , ψ c , P = 1.0 . Tabular value for pullout resistance is for a concrete compressive strength of 20 MPa ( 2,900 psi ). Pullout resistance for concrete compressive strength greater than 20 MPa ( 2,900 psi ) may be increased by multiplying the tabular pullout resistance by ( f ' c / 20 ) 0 . 35 for MPa or ( f ' c / 2,900 ) 0 . 35 for psi . NA ( not applicable ) denotes that pullout strength does not need to be considered for design .
7 Shear and seismic shear tests are all performed in cracked concrete member per ICC-ES AC193 section 9.4 and 9.6 respectively . Value of V sa (, eq ) < 0.6 A se , V f uta for all cases . Multiply V sa tabular value above by φ s R s , V to get V sar and V sar , eq .
D7.1.2
432 Anchor Fastening Technical Guide Edition 22 | 3.0 ANCHORING SYSTEMS | 3.3.13 HDI-P TZ FLUSH ANCHOR Hilti , Inc . 1-800-879-8000 | en español 1-800-879-5000 | www . hilti . com | Hilti ( Canada ) Corporation | www . hilti . ca | 1-800-363-4458