Product Technical Guides : US-EN Anchor Fastening - August 2021 | Page 416

Table 12 — Hilti KWIK Bolt 3 hot-dip galvanized design strength with concrete / pullout failure in uncracked concrete 1 , 2 , 3 , 4 , 5
Nominal anchor diameter in .
1 / 2
5 / 8
3 / 4
Effective embed . in . ( mm )
Nominal embed . in . ( mm ) ƒ ' c
= 2,500 psi lb ( kN ) ƒ ' c
= 3,000 psi lb ( kN )
Tension - фN n ƒ ' c
= 4,000 psi lb ( kN ) ƒ ' c
= 6,000 psi lb ( kN ) ƒ ' c
= 2,500 psi lb ( kN ) ƒ ' c
= 3,000 psi lb ( kN )
Shear - фV n ƒ ' c
= 4,000 psi lb ( kN ) ƒ ' c
= 6,000 psi lb ( kN )
2 2-1 / 4 2,205 2,415 2,790 3,420 2,375 2,605 3,005 3,680 ( 51 ) ( 57 ) ( 9.8 ) ( 10.7 ) ( 12.4 ) ( 15.2 ) ( 10.6 ) ( 11.6 ) ( 13.4 ) ( 16.4 ) 3-1 / 4 3-1 / 2 4,250 4,655 5,375 6,585 9,845 10,785 12,450 15,250 ( 83 ) ( 89 ) ( 18.9 ) ( 20.7 ) ( 23.9 ) ( 29.3 ) ( 43.8 ) ( 48.0 ) ( 55.4 ) ( 67.8 ) 3-1 / 8 3-1 / 2 4,200 4,605 5,315 6,510 9,280 10,165 11,740 14,380 ( 79 ) ( 89 ) ( 18.7 ) ( 20.5 ) ( 23.6 ) ( 29.0 ) ( 41.3 ) ( 45.2 ) ( 52.2 ) ( 64.0 ) 4 4-3 / 8 5,860 6,420 7,415 9,080 13,440 14,725 17,000 20,820 ( 102 ) ( 111 ) ( 26.1 ) ( 28.6 ) ( 33.0 ) ( 40.4 ) ( 59.8 ) ( 65.5 ) ( 75.6 ) ( 92.6 ) 3-3 / 4 4-1 / 4 5,665 6,205 7,165 8,775 12,200 13,365 15,430 18,900 ( 95 ) ( 108 ) ( 25.2 ) ( 27.6 ) ( 31.9 ) ( 39.0 ) ( 54.3 ) ( 59.5 ) ( 68.6 ) ( 84.1 ) 5 5-1 / 2 6,615 7,245 8,365 10,245 18,785 20,575 23,760 29,100
( 127 ) ( 140 ) ( 29.4 ) ( 32.2 ) ( 37.2 ) ( 45.6 ) ( 83.6 ) ( 91.5 ) ( 105.7 ) ( 129.4 )
1 See section 3.1.8 to convert design strength value to ASD value . 2 Linear interpolation between embedment depths and concrete compressive strengths is not permitted .
3 Apply spacing , edge distance , and concrete thickness factors in tables 23 to 25 as necessary . Compare to steel values in table 21 . The lesser of the values is to be used for the design .
4 Tabular values are for normal-weight concrete only . For lightweight concrete multiply design strength by λ a as follows : for sand-lightweight , λ = 0.68 ; for all-lightweight , λ = 0.60 5 Tabular values are for static loads only . Seismic design is not permitted for uncracked concrete .
Table 13 — Steel design strength for Hilti KWIK Bolt 3 hot-dip galvanized anchors 1 , 2
Nominal anchor diameter in .
1 / 2
5 / 8
3 / 4
Nominal embedment in . ( mm )
2-1 / 4
Tensile фN sa
3 lb ( kN )
Shear фV sa
4 lb ( kN ) 2,925
( 57 )
8,745
( 13.0 )
3-1 / 2
( 38.9 )
3,815
( 89 ) ( 17.0 ) 3-1 / 2 ( 89 ) 4-3 / 8 ( 111 ) 4-1 / 4 ( 108 ) 5-1 / 2 ( 140 )
1 See section 3.1.8 to convert design strength value to ASD value .
13,515 ( 60.1 )
19,080 ( 84.9 )
2 KWIK Bolt 3 carbon steel anchors are to be considered ductile steel elements . 3 Tensile фN sa
= ф A se , N f uta as noted in ACI 318 Chapter 17 . 4 Shear values determined by static shear tests with фV sa
< ф 0.60 A se , V f uta as noted in ACI 318 Chapter 17 .
7,565 ( 33.7 )
11,050 ( 49.2 )
412 Anchor Fastening Technical Guide Edition 22 | 3.0 ANCHORING SYSTEMS | 3.3.11 KWIK Bolt 3 ( KB 3 ) CARBON AND STAINLESS STEEL SCREW ANCHOR Hilti , Inc . 1-800-879-8000 | en español 1-800-879-5000 | www . hilti . com | Hilti ( Canada ) Corporation | www . hilti . ca | 1-800-363-4458