Product Technical Guides : US-EN Anchor Fastening - August 2021 | Page 302

3.3.5 KWIK BOLT TZ2 EXPANSION ANCHOR
PRODUCT DESCRIPTION
KWIK BOLT TZ2 Expansion anchor
Anchor System Features and Benefits
Carbon steel KB-TZ2
Stainless Steel 304 / 316 KB-TZ2
• IFU provides multiple installation methods including no hole cleaning with hammer drill , Hilti Dust Removal System ( DRS ) for virtually dustless installation ( OSHA 1926.1153 Table 1 compliant ) and core drilling installation .
• More accurate SafeSet™ installation when using the Hilti SIW-6AT-A22 impact wrench and the SI-AT-A22 Adaptive Torque Module .
• Product and length identification marks help facilitate quality control after installation .
• Maximized thread lengths and multiple embedment depths to accommodate various base plate thicknesses .
• Mechanical expansion allows immediate load application .
• Raised impact section ( dog point ) helps protect threads from damage during installation .
• Bolt meets ductility requirements of ACI 318 Section 2.3 .
• Functional coatings and profile on expansion wedges provide increased reliability .
Uncracked concrete
Cracked concrete
Grout-filled concrete masonry
Seismic Design Categories A-F
Fire sprinkler listings
Profis Engineering design software
Hollow Drill Bit and Adaptive Torque Tool ( AT )
Approvals / Listings
ICC-ES ( International Code Council )
• 2021 International Building Code / International Residential Code ( IBC / IRC )
• 2015 National Building Code of Canada ( NBC-C )
City of Los Angeles
Florida Building Code
FM ( Factory Mutual ) — Carbon steel KB-TZ2 only
UL and cUL ( Underwriters Laboratory ) — Carbon steel KB-TZ2 only
ANSI / MSS SP-58-2018
ESR-4266 in concrete per ACI 318 Ch . 17 / ACI 355.2 / ICC-ES AC193 ESR-4561 in grout-filled CMU per ICC-ES AC01 ELC-4266 in concrete per CSA A23.3 / ACI 355.2
2020 LABC Supplement ( within ESR-4266 & ESR-4561 )
2020 FBC Supplement with HVHZ ( within ESR-4266 & ESR-4561 )
Pipe hanger components for automatic sprinkler systems 3 / 8 ( up to 4-inch nominal pipe diameter ) 1 / 2 1 ( up to 8-inch nominal pipe diameter ) 3 / 4 ( up to 12-inch nominal pipe diameter )
Pipe hanger equipment for fire protection services 3 / 8 ( up to 4-inch nominal pipe diameter ) 1 / 2 1 ( up to 8-inch nominal pipe diameter ) 5 / 8 & 3 / 4 ( up to 12-inch nominal pipe diameter )
Anchors conform to ANSI / MSSP-58-2018 . Contact Hilti for more information .
LISTED
Pipe Hanger 757G
1 1 / 2-inch dia . with 1-1 / 2-inch effective embedment does not have FM or UL certification .
298 Anchor Fastening Technical Guide Edition 22 | 3.0 ANCHORING SYSTEMS | 3.3.5 KWIK BOLT TZ2 EXPANSION ANCHOR Hilti , Inc . 1-800-879-8000 | en español 1-800-879-5000 | www . hilti . com | Hilti ( Canada ) Corporation | www . hilti . ca | 1-800-363-4458