Table 31 — Hilti HVU2 adhesive factored resistance with lesser of concrete or bond failure for HIS-N and HIS-RN internally threaded inserts in uncracked concrete 1 , 2 , 3 , 4 , 5 , 6 , 7 , 8 , 9
Hammer drilling with carbide tipped drill bit , or Hilti TE-CD or TE-YD Hollow Drill Bit
Thread size
3 / 8-16 UNC
1 / 2-13 UNC
5 / 8-11 UNC
3 / 4-10 UNC
Effective embedment in . ( mm ) f ́c = 20 MPa ( 2,900 psi ) lb ( kN ) f ́c = 25 MPa ( 3,625 psi ) lb ( kN )
Tension — N r
f ́c = 30 MPa ( 4,350 psi ) lb ( kN ) f ́c = 40 MPa ( 5,800 psi ) lb ( kN ) f ́c = 20 MPa ( 2,900 psi ) lb ( kN ) f ́c = 25 MPa ( 3,625 psi ) lb ( kN )
Shear — V r
f ́c = 30 MPa ( 4,350 psi ) lb ( kN ) f ́c = 40 MPa ( 5,800 psi ) lb ( kN )
4-3 / 8 7,540 8,430 8,555 8,555 15,080 16,860 17,110 17,110 ( 110 ) ( 33.5 ) ( 37.5 ) ( 38.0 ) ( 38.0 ) ( 67.1 ) ( 75.0 ) ( 76.1 ) ( 76.1 )
5 9,135 10,210 11,185 12,115 18,265 20,420 22,370 24,225 ( 125 ) ( 40.6 ) ( 45.4 ) ( 49.8 ) ( 53.9 ) ( 81.3 ) ( 90.8 ) ( 99.5 ) ( 107.8 ) 6-3 / 4 14,485 16,195 17,740 20,340 28,970 32,390 35,480 40,675 ( 170 ) ( 64.4 ) ( 72.0 ) ( 78.9 ) ( 90.5 ) ( 128.9 ) ( 144.1 ) ( 157.8 ) ( 180.9 ) 8-1 / 8 19,180 21,445 23,490 26,735 38,360 42,890 46,985 53,465 ( 205 ) ( 85.3 ) ( 95.4 ) ( 104.5 ) ( 118.9 ) ( 170.6 ) ( 190.8 ) ( 209.0 ) ( 237.8 )
Table 32 — Hilti HVU2 adhesive factored resistance with lesser of concrete or bond failure for HIS-N and HIS-RN internally threaded inserts in cracked concrete 1 , 2 , 3 , 4 , 5 , 6 , 7 , 8 , 9 , 10
Hammer drilling with carbide tipped drill bit , or Hilti TE-CD or TE-YD Hollow Drill Bit
Thread size
3 / 8-16 UNC
1 / 2-13 UNC
5 / 8-11 UNC
3 / 4-10 UNC
Effective embedment in . ( mm ) f ́c = 20 MPa ( 2,900 psi ) lb ( kN ) f ́c = 25 MPa ( 3,625 psi ) lb ( kN )
Tension — N r
f ́c = 30 MPa ( 4,350 psi ) lb ( kN ) f ́c = 40 MPa ( 5,800 psi ) lb ( kN ) f ́c = 20 MPa ( 2,900 psi ) lb ( kN ) f ́c = 25 MPa ( 3,625 psi ) lb ( kN )
Shear — V r
f ́c = 30 MPa ( 4,350 psi ) lb ( kN ) f ́c = 40 MPa ( 5,800 psi ) lb ( kN )
4-3 / 8 4,325 4,585 4,810 5,180 8,655 9,170 9,615 10,360 ( 110 ) ( 19.2 ) ( 20.4 ) ( 21.4 ) ( 23.0 ) ( 38.5 ) ( 40.8 ) ( 42.8 ) ( 46.1 )
5 6,125 6,495 6,810 7,335 12,255 12,985 13,615 14,675 ( 125 ) ( 27.3 ) ( 28.9 ) ( 30.3 ) ( 32.6 ) ( 54.5 ) ( 57.8 ) ( 60.6 ) ( 65.3 ) 6-3 / 4 10,140 10,900 11,430 12,320 20,280 21,805 22,860 24,635 ( 170 ) ( 45.1 ) ( 48.5 ) ( 50.8 ) ( 54.8 ) ( 90.2 ) ( 97.0 ) ( 101.7 ) ( 109.6 ) 8-1 / 8 13,425 14,330 15,025 16,190 26,855 28,660 30,050 32,385 ( 205 ) ( 59.7 ) ( 63.7 ) ( 66.8 ) ( 72.0 ) ( 119.5 ) ( 127.5 ) ( 133.7 ) ( 144.0 )
1 See Section 3.1.8 for explanation on development of load values . 2 See Section 3.1.8 to convert design strength value to ASD value . 3 Linear interpolation between embedment depths and concrete compressive strengths is not permitted . 4 Apply spacing , edge distance , and concrete thickness factors in tables 19 – 20 as necessary to the above values . Compare to the steel values in table 30 .
The lesser of the values is to be used for the design .
5 Data is for temperature range A : Max . short term temperature = 130 ° F ( 55 ° C ), max . long term temperature = 110 ° F ( 43 ° C ). For temperature range B : Max . short term temperature = 176 ° F ( 80 ° C ), max . long term temperature = 110 ° F ( 43 ° C ) multiply above value by 0.93 . For temperature range C : Max . short term temperature = 248 ° F ( 120 ° C ), max . long term temperature = 162 ° F ( 72 ° C ) multiply above value by 0.58 . Short term elevated concrete temperatures are those that occur over brief intervals , e . g ., as a result of diurnal cycling . Long term concrete temperatures are roughly constant over significant periods of time . 6 Tabular values are for dry or water saturated concrete conditions . 7 Tabular values are for short term loads only . For sustained loads including overhead use , see Section 3.1.8 . 8 Tabular values are for normal weight concrete only . For lightweight concrete multiply design strength by λ a as follows :
For sand-lightweight , λ a = 0.51 . For all-lightweight , λ a
= 0.45 . 9 Tabular values are for horizontal and vertical downward direction only . For overhead ( vertical up ) installation , tabular values must be multiplied by 0.70 . 10 Tabular values are for static loads only . Seismic design is not permitted for uncracked concrete . For seismic loads , multiply cracked concrete tabular values in tension and shear by
α seis
= 0.75 . See section 3.1.8 for additional information on seismic applications .
252 Anchor Fastening Technical Guide Edition 22 | 3.0 ANCHORING SYSTEMS | 3.2.6 HVU2 CAPSULE ADHESIVE ANCHORING SYSTEM Hilti , Inc . 1-800-879-8000 | en español 1-800-879-5000 | www . hilti . com | Hilti ( Canada ) Corporation | www . hilti . ca | 1-800-363-4458