Product Technical Guides : US-EN Anchor Fastening - August 2021 | Page 252

Table 24 — Hilti HVU2 adhesive factored resistance with lesser of concrete or bond failure for threaded rod in uncracked concrete 1 , 2 , 3 , 4 , 5 , 6 , 7 , 8 , 9
Hammer drilling with carbide tipped drill bit , or Hilti TE-CD or TE-YD Hollow Drill Bit
Nominal anchor diameter in .
3 / 8
1 / 2
5 / 8
3 / 4
7 / 8
1
Effective embedment in . ( mm ) f ́c = 20 MPa ( 2,900 psi ) lb ( kN ) f ́c = 25 MPa ( 3,625 psi ) lb ( kN )
Tension — N r
f ́c = 30 MPa ( 4,350 psi ) lb ( kN ) f ́c = 40 MPa ( 5,800 psi ) lb ( kN ) f ́c = 20 MPa ( 2,900 psi ) lb ( kN ) f ́c = 25 MPa ( 3,625 psi ) lb ( kN )
Shear — V r
f ́c = 30 MPa ( 4,350 psi ) lb ( kN ) f ́c = 40 MPa ( 5,800 psi ) lb ( kN )
3-1 / 2 4,110 4,360 4,570 4,925 8,225 8,715 9,140 9,850 ( 89 ) ( 18.3 ) ( 19.4 ) ( 20.3 ) ( 21.9 ) ( 36.6 ) ( 38.8 ) ( 40.7 ) ( 43.8 ) 4-1 / 4 7,330 8,195 8,975 10,365 14,660 16,390 17,955 20,730 ( 108 ) ( 32.6 ) ( 36.5 ) ( 39.9 ) ( 46.1 ) ( 65.2 ) ( 72.9 ) ( 79.9 ) ( 92.2 )
5 9,355 10,455 11,455 13,225 18,705 20,915 22,910 26,455 ( 127 ) ( 41.6 ) ( 46.5 ) ( 51.0 ) ( 58.8 ) ( 83.2 ) ( 93.0 ) ( 101.9 ) ( 117.7 ) 6-5 / 8 14,265 15,950 17,470 20,175 28,530 31,900 34,940 40,350 ( 168 ) ( 63.5 ) ( 70.9 ) ( 77.7 ) ( 89.7 ) ( 126.9 ) ( 141.9 ) ( 155.4 ) ( 179.5 ) 6-5 / 8 14,265 15,950 17,470 20,175 28,530 31,900 34,940 40,350 ( 168 ) ( 63.5 ) ( 70.9 ) ( 77.7 ) ( 89.7 ) ( 126.9 ) ( 141.9 ) ( 155.4 ) ( 179.5 ) 8-1 / 4 19,825 22,165 24,280 28,035 39,645 44,325 48,555 56,070 ( 210 ) ( 88.2 ) ( 98.6 ) ( 108.0 ) ( 124.7 ) ( 176.4 ) ( 197.2 ) ( 216.0 ) ( 249.4 )
( 10 )
11
30,520
34,120
37,380
43,160
61,040
68,245
74,760
86,325
1-1 / 4
( 279 )
( 135.8 )
( 151.8 )
( 166.3 )
( 192.0 )
( 271.5 )
( 303.6 )
( 332.5 )
( 384.0 )
Table 25 — Hilti HVU2 adhesive factored resistance with lesser of concrete or bond failure for threaded rod in cracked concrete 1 , 2 , 3 , 4 , 5 , 6 , 7 , 8 , 9 , 11
Hammer drilling with carbide tipped drill bit , or Hilti TE-CD or TE-YD Hollow Drill Bit
Nominal anchor diameter in .
1 / 2
5 / 8
3 / 4
7 / 8
1
Effective embedment in . ( mm ) f ́c = 20 MPa ( 2,900 psi ) lb ( kN ) f ́c = 25 MPa ( 3,625 psi ) lb ( kN )
Tension — N r
f ́c = 30 MPa ( 4,350 psi ) lb ( kN ) f ́c = 40 MPa ( 5,800 psi ) lb ( kN ) f ́c = 20 MPa ( 2,900 psi ) lb ( kN ) f ́c = 25 MPa ( 3,625 psi ) lb ( kN )
Shear — V r
f ́c = 30 MPa ( 4,350 psi ) lb ( kN ) f ́c = 40 MPa ( 5,800 psi ) lb ( kN )
4-1 / 4 4,675 4,825 4,950 5,155 9,355 9,650 9,900 10,305 ( 108 ) ( 20.8 ) ( 21.5 ) ( 22.0 ) ( 22.9 ) ( 41.6 ) ( 42.9 ) ( 44.0 ) ( 45.8 )
5 6,545 7,095 7,280 7,580 13,095 14,190 14,560 15,155 ( 127 ) ( 29.1 ) ( 31.6 ) ( 32.4 ) ( 33.7 ) ( 58.2 ) ( 63.1 ) ( 64.8 ) ( 67.4 ) 6-5 / 8 9,985 11,165 11,575 12,050 19,970 22,330 23,150 24,100 ( 168 ) ( 44.4 ) ( 49.7 ) ( 51.5 ) ( 53.6 ) ( 88.8 ) ( 99.3 ) ( 103.0 ) ( 107.2 ) 6-5 / 8 9,985 11,165 12,230 14,060 19,970 22,330 24,460 28,115 ( 168 ) ( 44.4 ) ( 49.7 ) ( 54.4 ) ( 62.5 ) ( 88.8 ) ( 99.3 ) ( 108.8 ) ( 125.1 ) 8-1 / 4 13,875 15,515 16,995 19,625 27,755 31,030 33,990 39,250 ( 210 ) ( 61.7 ) ( 69.0 ) ( 75.6 ) ( 87.3 ) ( 123.4 ) ( 138.0 ) ( 151.2 ) ( 174.6 )
( 10 )
11
21,365
23,885
26,165
30,215
42,730
47,770
52,330
60,425
1-1 / 4
( 279 )
( 95.0 )
( 106.2 )
( 116.4 )
( 134.4 )
( 190.1 )
( 212.5 )
( 232.8 )
( 268.8 )
1 See Section 3.1.8 for explanation on development of load values . 2 See Section 3.1.8 to convert design strength value to ASD value . 3 Linear interpolation between embedment depths and concrete compressive strengths is not permitted . 4 Apply spacing , edge distance , and concrete thickness factors in tables 7 – 10 as necessary . Compare to the steel values in table 23 .
The lesser of the values is to be used for the design .
5 Data is for temperature range A : Max . short term temperature = 130 ° F ( 55 ° C ), max . long term temperature = 110 ° F ( 43 ° C ). For temperature range B : Max . short term temperature = 176 ° F ( 80 ° C ), max . long term temperature = 110 ° F ( 43 ° C ) multiply above value by 0.93 . For temperature range C : Max . short term temperature = 248 ° F ( 120 ° C ), max . long term temperature = 162 ° F ( 72 ° C ) multiply above value by 0.58 . Short term elevated concrete temperatures are those that occur over brief intervals , e . g ., as a result of diurnal cycling . Long term concrete temperatures are roughly constant over significant periods of time . 6 Tabular values are for dry or water saturated concrete conditions . 7 Tabular values are for short term loads only . For sustained loads including overhead use , see Section 3.1.8 . 8 Tabular values are for normal weight concrete only . For lightweight concrete multiply design strength by λ a as follows :
For sand-lightweight , λ a = 0.51 . For all-lightweight , λ a
= 0.45 . 9 For 3 / 8-in to 1-in dia . threaded rods , tabular values are for horizontal and vertical downward direction only . For overhead ( vertical up ) installation , tabular values must be multiplied by 0.70 . 10 1-1 / 4-in diameter rods to be installed in generally vertically downward direction only . 11 Tabular values are for static loads only . Seismic design is not permitted for uncracked concrete . For seismic loads , multiply cracked concrete tabular values in tension and shear by α seis
= 0.75 . See section 3.1.8 for additional information on seismic applications .
248 Anchor Fastening Technical Guide Edition 22 | 3.0 ANCHORING SYSTEMS | 3.2.6 HVU2 CAPSULE ADHESIVE ANCHORING SYSTEM Hilti , Inc . 1-800-879-8000 | en español 1-800-879-5000 | www . hilti . com | Hilti ( Canada ) Corporation | www . hilti . ca | 1-800-363-4458