Product Technical Guides : US-EN Anchor Fastening - August 2021 | Page 248

Table 17 — Hilti HVU2 adhesive design strength with lesser of concrete or bond failure for HIS-N and HIS-RN internally threaded inserts in uncracked concrete 1 , 2 , 3 , 4 , 5 , 6 , 7 , 8 , 9
Diamond core drilling
Thread size
3 / 8-16 UNC
1 / 2-13 UNC
5 / 8-11 UNC
3 / 4-10 UNC
Effective embedment in . ( mm ) f ́c = 2500 psi ( 17.2 Mpa ) lb ( kN ) f ́c = 3000 psi ( 20.7 Mpa ) lb ( kN )
Tension — ФN n
f ́c = 4000 psi ( 27.6 Mpa ) lb ( kN ) f ́c = 6000 psi ( 41.4 Mpa ) lb ( kN ) f ́c = 2500 psi ( 17.2 Mpa ) lb ( kN ) f ́c = 3000 psi ( 20.7 Mpa ) lb ( kN )
Shear — ФV n
f ́c = 4000 psi ( 27.6 Mpa ) lb ( kN ) f ́c = 6000 psi ( 41.4 Mpa ) lb ( kN )
4-3 / 8 7,140 7,820 8,215 8,215 15,375 16,840 17,700 17,700 ( 111 ) ( 31.8 ) ( 34.8 ) ( 36.5 ) ( 36.5 ) ( 68.4 ) ( 74.9 ) ( 78.7 ) ( 78.7 ) 5 8,720 9,555 11,030 11,700 18,785 20,575 23,760 25,205 ( 127 ) ( 38.8 ) ( 42.5 ) ( 49.1 ) ( 52.0 ) ( 83.6 ) ( 91.5 ) ( 105.7 ) ( 112.1 ) 6-3 / 4 13,680 14,985 17,305 19,505 29,460 32,275 37,265 42,010 ( 171 ) ( 60.9 ) ( 66.7 ) ( 77.0 ) ( 86.8 ) ( 131.0 ) ( 143.6 ) ( 165.8 ) ( 186.9 ) 8-1 / 8 18,065 19,790 22,850 25,590 38,910 42,620 49,215 55,115 ( 206 ) ( 80.4 ) ( 88.0 ) ( 101.6 ) ( 113.8 ) ( 173.1 ) ( 189.6 ) ( 218.9 ) ( 245.2 )
Table 18 — Hilti HVU2 adhesive design strength with lesser of concrete or bond failure for HIS-N and HIS-RN internally threaded inserts in cracked concrete 1 , 2 , 3 , 4 , 5 , 6 , 7 , 8 , 9 , 10
Diamond core drilling
Thread size
3 / 8-16 UNC
1 / 2-13 UNC
5 / 8-11 UNC
3 / 4-10 UNC
Effective embedment in . ( mm ) f ́c = 2500 psi ( 17.2 Mpa ) lb ( kN ) f ́c = 3000 psi ( 20.7 Mpa ) lb ( kN )
Tension — ФN n
f ́c = 4000 psi ( 27.6 Mpa ) lb ( kN ) f ́c = 6000 psi ( 41.4 Mpa ) lb ( kN ) f ́c = 2500 psi ( 17.2 Mpa ) lb ( kN ) f ́c = 3000 psi ( 20.7 Mpa ) lb ( kN )
Shear — ФV n
f ́c = 4000 psi ( 27.6 Mpa ) lb ( kN ) f ́c = 6000 psi ( 41.4 Mpa ) lb ( kN )
4-3 / 8 2,935 3,030 3,190 3,435 6,315 6,525 6,875 7,395 ( 111 ) ( 13.1 ) ( 13.5 ) ( 14.2 ) ( 15.3 ) ( 28.1 ) ( 29.0 ) ( 30.6 ) ( 32.9 ) 5 4,175 4,315 4,545 4,890 8,995 9,295 9,790 10,530 ( 127 ) ( 18.6 ) ( 19.2 ) ( 20.2 ) ( 21.8 ) ( 40.0 ) ( 41.3 ) ( 43.5 ) ( 46.8 ) 6-3 / 4 6,960 7,195 7,575 8,150 14,990 15,495 16,315 17,550 ( 171 ) ( 31.0 ) ( 32.0 ) ( 33.7 ) ( 36.3 ) ( 66.7 ) ( 68.9 ) ( 72.6 ) ( 78.1 ) 8-1 / 8 9,135 9,440 9,940 10,690 19,670 20,325 21,405 23,030 ( 206 ) ( 40.6 ) ( 42.0 ) ( 44.2 ) ( 47.6 ) ( 87.5 ) ( 90.4 ) ( 95.2 ) ( 102.4 )
1 See Section 3.1.8 for explanation on development of load values . 2 See Section 3.1.8 to convert design strength value to ASD value . 3 Linear interpolation between embedment depths and concrete compressive strengths is not permitted . 4 Apply spacing , edge distance , and concrete thickness factors in tables 19 – 20 as necessary to the above values . Compare to the steel values in table 14 .
The lesser of the values is to be used for the design .
5 Data is for temperature range A : Max . short term temperature = 130 ° F ( 55 ° C ), max . long term temperature = 110 ° F ( 43 ° C ). For temperature range B : Max . short term temperature = 176 ° F ( 80 ° C ), max . long term temperature = 110 ° F ( 43 ° C ) multiply above value by 0.94 . For temperature range C : Max . short term temperature = 248 ° F ( 120 ° C ), max . long term temperature = 162 ° F ( 72 ° C ) multiply above value by 0.60 . Short term elevated concrete temperatures are those that occur over brief intervals , e . g ., as a result of diurnal cycling . Long term concrete temperatures are roughly constant over significant periods of time . 6 Tabular values are for dry or water saturated concrete conditions . 7 Tabular values are for short term loads only . For sustained loads including overhead use , see Section 3.1.8 . 8 Tabular values are for normal weight concrete only . For lightweight concrete multiply design strength by λ a as follows :
For sand-lightweight , λ a = 0.51 . For all-lightweight , λ a
= 0.45 . 9 Tabular values are for horizontal and vertical downward direction only . For overhead ( vertical up ) installation , tabular values must be multiplied by 0.70 . 10 Tabular values are for static loads only . Seismic design is not permitted for uncracked concrete . For seismic loads , multiply cracked concrete tabular values in tension and shear by α seis
= 0.75 . See section 3.1.8 for additional information on seismic applications .
244 Anchor Fastening Technical Guide Edition 22 | 3.0 ANCHORING SYSTEMS | 3.2.6 HVU2 CAPSULE ADHESIVE ANCHORING SYSTEM Hilti , Inc . 1-800-879-8000 | en español 1-800-879-5000 | www . hilti . com | Hilti ( Canada ) Corporation | www . hilti . ca | 1-800-363-4458