Product Technical Guides : US-EN Anchor Fastening - August 2021 | Page 474

h deck , min
( see Table 1 )
Min . 3,000 psi normal-weight or sand-light weight concrete
Max . 3 ”
Min . 1-3 / 4 ”
KCC-MD SP 3 / 8 ” KCC-MD SP 1 / 2 ”
Min . 20 ga . steel deck
Figure 5A — Installation of KCC-MD inserts in the soffit of concrete filled metal deck floor and roof assemblies-over upper flute ( B-deck and W-deck )
h deck , min
( see Table 1 )
Min . 3,000 psi normal-weight or sand-light weight concrete
Max . 3 ”
Min . 1-3 / 4 ”
KCC-MD SP -3 / 8 ”
Min . 20 ga . steel deck
Min . 11 / 16 ”
h deck , min
( see Table 1 )
Min . 3,000 psi normal-weight or sand-light weight concrete
Max . 3 ”
Min . 4-1 / 2 ”
Min . 7 / 8 ”
KCC-MD SP 3 / 8 ” KCC-MD SP 1 / 2 ”
Min . 20 ga . steel deck
h deck , min
( see Table 1 )
Min . 3,000 psi normal-weight or sand-light weight concrete
Max . 3 ”
Min . 3-7 / 8 ”
Min . 1 / 2 ”
KCC-MD LP 3 / 8 ” KCC-MD LP 1 / 2 ”
Min . 20 ga . steel deck
Figure 5B — Installation of KCC-MD inserts in the soffit of concrete filled metal deck floor and roof assemblies-over lower flute ( W-deck )
470 Anchor Fastening Technical Guide Edition 22 | 3.0 ANCHORING SYSTEMS | 3.3.17 KCC-WF AND KCC-MD CAST-IN ANCHOR Hilti , Inc . 1-800-879-8000 | en español 1-800-879-5000 | www . hilti . com | Hilti ( Canada ) Corporation | www . hilti . ca | 1-800-363-4458